Schmersal

101215387

BDF200-ST1-AS-NHK-LMRD-LTWH-LTBU
101215387
101215387
101215387
101215387
101215387
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:

Electrical data - AS-Interface specification

Note (AS-i Parameter bits)
Set the parameter outputs to "1111" (0xF) | FID: periphery error
AS-i Version (Safety-Slave)
V 3.0
AS-i Profile (Safety-Slave)
S-7.B.F.F
AS-i Input, Channel 1 (Safety-Slave)
Data bits DI 0 / DI 1 = dynamic code transmission
AS-i Input, Channel 2 (Safety-Slave)
Data bits DI 2 / DI 3 = dynamic code transmission
AS-i Output, DO 0 (Safety-Slave)
Indicator lamp G24 red
AS-i Output, DO 1 (Safety-Slave)
Indicator lamp G24 green
AS-i Output, DO 2 (Safety-Slave)
No Function
AS-i Output, DO 3 (Safety-Slave)
No Function
AS-i AS-i Parameter bits (Safety-Slave), P0 ... P3
No function
AS-i Version (A/B Slave)
V 3.0
AS-i Profile (A/B Slave)
S-7.A.7.F
AS-i Input, DI 0 (A/B Slave)
Command device Position 4
AS-i Input, DI 1 (A/B Slave)
Command device Position 3
AS-i Input, DI 2 (A/B Slave)
Command device Position 2
AS-i Input, DI 3 (A/B Slave)
Command device Position 2
AS-i Output, DO 0 (A/B Slave)
Illuminated signal position 4
AS-i Output, DO 2 (A/B Slave)
Illuminated signal position 2
AS-i Output, DO 1 (A/B Slave)
Illuminated signal position 3
AS-i Output, DO 3 (A/B Slave)
No Function
AS-i AS-i Parameter bits (A/B Slave), P0 ... P3
No function
AS-i Input module address
0
Note (AS-i Input module address)
Preset to address 0, can be changed through AS-interface bus master or hand-held programming device
Note
Both AS-i slaves can be enabled and disabled through the integrated DIP switch. The addressing must take place via the M12 connector.

Mechanical data - Dimensions

Width
40 mm
Height
69 mm
Depth
233.5 mm

Pin assignment

PIN 1
AS-Interface +
PIN 2
n.c.
PIN 3
AS-Interface -
PIN 4
n.c.

Ambient conditions - Insulation values

Rated insulation voltage U
32 VDC
Rated impulse withstand voltage U
0.8 kV
Overvoltage category
III
Degree of pollution
3

General data - Features

Indicator lamp
No

General data

Standards
EN IEC 62026-2 | EN ISO 13849-1 | EN ISO 13850 | EN IEC 60947-5-1 | EN IEC 61508
Climatic stress
DIN EN 60068
Enclosure material
Plastic, glass-fibre reinforced thermoplastic, self-extinguishing
Gross weight
280 g
Reaction time, maximum
100 ms
Positions used, position 1
Emergency stop, with protective collar
Positions used, position 2
Illuminated signal, red
Positions used, position 3
Illuminated pushbutton, white
Positions used, position 4
Illuminated pushbutton, blue

Safety classification

Standards
EN IEC 61508
Performance Level, up to
e
Category
4
PFH value
1.40 x 10⁻⁸ /h
Note (PFH-value)
up to max. 5,000 switching cycles/year
Safety Integrity Level (SIL), suitable for applications in
3
Mission time
20 Year(s)

Electrical data - AS Interface

Rated operating voltage
18 ... 31.6 VDC (Protection against polarity reversal)
AS-i Current consumption, maximum
150 mA

Ambient conditions

Degree of protection
IP65
Ambient temperature
-25 ... +65 °C
Storage and transport temperature, minimum
-25 °C
Storage and transport temperature, maximum
+85 °C
Resistance to vibrations
10 … 150 Hz, amplitude 0.35 mm / 5 g
Restistance to shock
15 g / 11 ms
Protection class
II

Mechanical data - Connection technique

Termination
Connector plug M12, 4-pole, (A-coding)

Mechanical data

Mechanical life, Emergency-Stop button
100,000 Operations
Mechanical life, Command devices
1,000,000 Operations

Specifications

Width
40 mm
Height
69 mm
Depth
233.5 mm

Approvals - Standards

Certificates
TÜV | cULus | ASi-SaW