Schmersal
103016678
BWU3635
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Product Conditions:
Electrical data - AS-Interface specification
- AS-i Specification
- Safety-Slave
- AS-i Version
- V 2.1
- AS-i Profile
- S-7.B.F.1
- AS-i Input, Channel 1
- Data bits DI 0 / DI 1 = dynamic code transmission
- AS-i Input, Channel 2
- Data bits DI 2 / DI 3 = dynamic code transmission
- AS-i Outputs, DO 0
- Digital output, Solenoid control
- AS-i Outputs, DO 1 … DO 3
- No Function
- AS-i Parameter bits, P0
- Control system watchdog
- AS-i Parameter bits, P1
- Diagnostics signal safety switchgear (inverted)
- AS-i Parameter bits, P2 ... P3
- No function
- Note (AS-i Parameter bits)
- Set the parameter outputs to "1111" (0xF)
- AS-i Input module address
- 0
- Note (AS-i Input module address)
- Preset to address 0, can be changed through AS-interface bus master or hand-held programming device
Mechanical data - Dimensions
- Width
- 60 mm
- Height
- 45 mm
- Depth
- 19 mm
General data - Features
- Safety functions
- Yes
- Integral system diagnostics, status
- Yes
General data
- Standards
- EN IEC 62026-2 | EN IEC 62061 | EN ISO 13849-1
- Enclosure material
- Plastic
- Gross weight
- 141 g
- Reaction time, maximum
- 11 ms
Safety classification
- Standards
- EN IEC 62061
- Performance Level, up to
- e
- Category
- 4
- PFH value
- 5.18 x 10⁻⁹ /h
- PFD value
- 6.19 x 10⁻⁷
- Safety Integrity Level (SIL), suitable for applications in
- 3
- Mission time
- 20 Year(s)
Electrical data - AS Interface
- Rated operating voltage
- 21.6 ... 31.6 VDC
- AS-i Current consumption, maximum
- 60 mA
Ambient conditions
- Degree of protection
- IP67
- Ambient temperature
- -20 ... +60 °C
- Storage and transport temperature, minimum
- -30 °C
- Storage and transport temperature, maximum
- +85 °C
- Resistance to vibrations
- 10 … 55 Hz, amplitude 0.5 mm
- Restistance to shock
- 15 g / 11 ms
Mechanical data - Connection technique
- Termination
- Cable connector M12, 8-pole, A-coded
- Length of cable
- 1 m
- Material of the cable
- PUR
Specifications
- Width
- 60 mm
- Height
- 45 mm
- Depth
- 19 mm
Electrical data - Auxiliary voltage
- Operating voltage
- 24 VDC -15 % / +10 % (stabilised PELV power supply)
- Rated operating voltage
- 24 VDC
Status indication
- Note (LED switching conditions display)
- (1) green/red LED (AS-i duo LED): Supply voltage / communication error / slave address = 0 / periphery error detected | (2) LED green: AUX-Power available | (3) LED yellow: S1 = Status safety input 1 | (4) LED yellow: S2 = Status safety input 2 | (5) LED yellow: I1 = Status input I1 | (6) LED yellow: o1 = Status output o1