IC60N - miniature circuit breaker - 2P - 10A - C curve
A9F79210
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
A total of 182 Parts In-Stock from 16 Distributors
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
€11.56

Additional Information

Part Number
A9F79210

Contractual Warranty

Warranty Period
18 months

Environment

IP Degree of Protection
IP20 conforming to EN 60529 || IP20 conforming to IEC 60529
Pollution Degree
3 conforming to EN 60947-2 || 3 conforming to IEC 60947-2
Overvoltage Category
IV
Tropicalisation
2 conforming to IEC 60068-1
Relative Humidity
95 % ( 55 °C )
Operating Altitude
0...2000 m
Ambient Air Temperature for Operation
-35...70 °C
Ambient Air Temperature for Storage
-40...85 °C

Offer Sustainability

Sustainable Offer Status
Green Premium product
Product Environmental Profile
Available
Product End of Life Instructions
Need no specific recycling operations

Complementary

Network Frequency
50/60 Hz
Magnetic Tripping Limit
8 x In +/- 20 %
[Ics] Rated Service Breaking Capacity
6000 A 100 % x Icu conforming to IEC 60898-1 - 400 V AC 50/60 Hz || 10 kA 100 % x Icu conforming to IEC 60947-2 - 72...125 V DC || 10 kA 100 % x Icu conforming to EN 60947-2 - 72...125 V DC || 6000 A 100 % x Icu conforming to EN 60898-1 - 400 V AC 50/60 Hz || 4.5 kA 75 % x Icu conforming to IEC 60947-2 - 440 V AC 50/60 Hz || 15 kA 75 % x Icu conforming to EN 60947-2 - 220...240 V AC 50/60 Hz || 7.5 kA 75 % x Icu conforming to EN 60947-2 - 380...415 V AC 50/60 Hz || 4.5 kA 75 % x Icu conforming to EN 60947-2 - 440 V AC 50/60 Hz || 15 kA 75 % x Icu conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz || 7.5 kA 75 % x Icu conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz || 27 kA 75 % x Icu conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz || 27 kA 75 % x Icu conforming to EN 60947-2 - 12...133 V AC 50/60 Hz
Limitation Class
3 conforming to EN 60898-1 || 3 conforming to IEC 60898-1
[Ui] Rated Insulation Voltage
500 V AC 50/60 Hz conforming to IEC 60947-2 || 500 V AC 50/60 Hz conforming to EN 60947-2
[Uimp] Rated Impulse Withstand Voltage
6 kV conforming to EN 60947-2 || 6 kV conforming to IEC 60947-2
Contact Position Indicator
Yes
Control Type
Toggle
Local Signalling
Trip indicator
Mounting Mode
Fixed
Mounting Support
DIN rail
Comb Busbar and Distribution Block Compatibility
YES top or bottom
9 mm Pitches
4
Height
85 mm
Width
36 mm
Depth
78.5 mm
Product Weight
0.25 kg
Colour
White
Mechanical Durability
20000 cycles
Electrical Durability
10000 cycles
Connections - Terminals
Single terminal, top or bottom rigid wire(s) 1...25 mm² max || Single terminal, top or bottom flexible wire(s) 1...16 mm² max
Wire Stripping Length
14 mm top or bottom
Tightening Torque
2 N.m top or bottom
Earth-leakage Protection
Separate block

Main

Device Application
Distribution
Range
Acti 9
Product Name
Acti 9 iC60
Product or Component Type
Miniature circuit-breaker
Device Short Name
IC60N
Poles Description
2P
Number of Protected Poles
2
[In] Rated Current
10 A
Network Type
AC || DC
Trip Unit Technology
Thermal-magnetic
Curve Code
C
Breaking Capacity
6 kA Icu conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz || 10 kA Icu conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz || 20 kA Icu conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz || 6000 A Icn conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz || 36 kA Icu conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz || 10 kA Icu conforming to EN/IEC 60947-2 - <= 125 V DC || 36 kA Icu conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz
Utilisation Category
Category A conforming to EN 60947-2 || Category A conforming to IEC 60947-2
Suitability for Isolation
Yes conforming to EN 60947-2 || Yes conforming to IEC 60947-2 || Yes conforming to EN 60898-1 || Yes conforming to IEC 60898-1
Standards
EN 60898-1 || EN 60947-2 || IEC 60898-1 || IEC 60947-2

Documents

Data Sheet

Download

CAD Models

Trace parts
Trace parts
Download

Related products