Schneider Electric

ATV340D30N4E

variable speed drive, Altivar Machine ATV340, 30kW, heavy duty, 400V, 3 phases, Ethernet
ATV340D30N4E
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
$1,664.33
1
Payment methods:
A total of 125 Parts In-Stock from 34 Distributors
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
€903.27

Additional Information

Part Number
ATV340D30N4E
UNSPSC
39122001
Tariff Code
8504404000
Country of Origin
CN

Complementary

Prospective Line Isc
50 kA
Power Dissipation In W
natural convection 77 W 380 V 4 kHz heavy duty) || forced convection 640 W 380 V 4 kHz heavy duty) || natural convection 90 W 380 V 4 kHz normal duty) || forced convection 796 W 380 V 4 kHz normal duty)
Line Current
66.2 A 380 V normal duty) || 57.3 A 480 V normal duty) || 54.8 A 380 V heavy duty) || 48.3 A 480 V heavy duty)
Line Current
66.2 A 380 V with internal line choke normal duty) || 57.3 A 480 V with internal line choke normal duty) || 66.2 A 380 V with internal line choke heavy duty) || 57.3 A 480 V with internal line choke heavy duty) || 54.8 A || 48.3 A
Analogue Output Type
software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 500 Ohm 10 bits
Discrete Output Type
programmable output DQ1, DQ2 30 V DC 100 mA
Electrical Connection
screw terminal 35...50 mm² line side || screw terminal 25...50 mm² DC bus || screw terminal 35...50 mm² motor || screw terminal 0.75...1.5 mm² control
Asynchronous Motor Control Profile
variable torque standard || optimized torque mode || constant torque standard
Maximum Switching Current
relay output R1C resistive, cos phi = 1 3 A 250 V AC || relay output R1C resistive, cos phi = 1 3 A 30 V DC || relay output R1C inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1C inductive, cos phi = 0.4 7 ms 2 A 30 V DC || relay output R2C resistive, cos phi = 1 5 A 250 V AC || relay output R2C resistive, cos phi = 1 5 A 30 V DC || relay output R2C inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R2C inductive, cos phi = 0.4 7 ms 2 A 30 V DC
4 Quadrant Operation Possible
true
Apparent Power
47.6 kVA 480 V normal duty) || 40.2 kVA 480 V heavy duty)
Net Weight
27.9 kg
Type Of Polarization
no impedance
Relay Output Type
relay outputs R1A || relay outputs R1C 100000 cycles || relay outputs R2A || relay outputs R2C 100000 cycles
Switching Frequency
2...16 kHz adjustable || 4...16 kHz with derating factor
Maximum Transient Current
89.4 A 60 s normal duty) || 89.4 A 2 s normal duty) || 92.3 A 60 s heavy duty) || 92.3 A 2 s heavy duty)
Analogue Input Number
3
Motor Slip Compensation
automatic whatever the load || not available in permanent magnet motor law || adjustable || can be suppressed
Discrete Output Number
1.0
Method Of Access
slave Modbus RTU || slave Modbus TCP
Number Of Addresses
1-247
Discrete Input Number
8
With Safety Function Safe Stop 1 (Ss1)
true
Width
213.0 mm
Transmission Rate
4.8 kbit/s || 9.6 kbit/s || 19.2 kbit/s || 38.4 kbit/s
Depth
262.0 mm
Analogue Input Type
AI1 software-configurable current 0...20 mA 250 Ohm 12 bits || AI1 software-configurable temperature probe or water level sensor || AI1 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits || AI2 software-configurable voltage - 10...10 V DC 31.5 kOhm 12 bits
Electrical Connection
line side screw terminal 35...50 mm² AWG 3...AWG 1 || DC bus screw terminal 25...50 mm² AWG 4...AWG 1 || motor screw terminal 35...50 mm² AWG 3...AWG 1 || control screw terminal 0.75...1.5 mm² AWG 18...AWG 16
Maximum Output Frequency
0.599 kHz
With Safety Function Safe Brake Management (Sbc/Sbt)
true
Height
660.0 mm
Acceleration And Deceleration Ramps
linear adjustable separately from 0.01...9999 s || S, U or customized
Maximum Output Voltage
480 V
Base Load Current At High Overload
61.5 A
Transmission Frame
RTU
Relay Output Number
3
With Safety Function Safe Torque Off (Sto)
true
Data Format
8 bits, configurable odd, even or no parity
Base Load Current At Low Overload
74.5 A
Connector Type
3 RJ45
Pollution Degree
2 IEC 61800-5-1
Analogue Output Number
2
Physical Interface
2-wire RS 485
Minimum Switching Current
relay output R1B 5 mA 24 V DC || relay output R2C 5 mA 24 V DC
Discrete Input Logic
16 preset speeds
Continuous Output Current
74.5 A 4 kHz normal duty || 61.5 A 4 kHz heavy duty
Brake Chopper Integrated
true
Output Voltage
<= power supply voltage
Nominal Switching Frequency
4 kHz
Braking To Standstill
by DC injection
Discrete Input Type
PTI safe torque off 0-30 kHz, 24 V DC 30 V) || DI1...DI5 programmable as pulse input, 24 V DC 30 V)3.5 kOhm || programmable
Protection Type
thermal protection motor || safe torque off motor || motor phase loss motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent drive || output overcurrent between motor phase and earth drive || output overcurrent between motor phases drive || short-circuit between motor phase and earth drive || short-circuit between motor phases drive || motor phase loss drive || DC Bus overvoltage drive || line supply overvoltage drive || line supply undervoltage drive || input supply loss drive || exceeding limit speed drive || break on the control circuit drive
With Safety Function Safely Limited Speed (Sls)
true
Synchronous Motor Control Profile
reluctance motor || permanent magnet motor

Specifications

Variant
standard version
Product Or Component Type
variable speed drive
Ip Degree Of Protection
IP20
Phase
3 phase
Communication Port Protocol
EtherNet/IP || Modbus TCP || Modbus serial
Nominal Output Current
61.5 A
Product Specific Application
machine
Maximum Horse Power Rating
50 hp normal duty || 40 hp heavy duty
Supply Frequency
50...60 Hz +/- 5 %
Option Card
communication module, PROFINET || communication module, DeviceNet || communication module, CANopen || communication module, EtherCAT
Degree Of Protection
UL type 1
Range Of Product
Altivar Machine ATV340
Motor Power Kw
37 kW normal duty || 30 kW heavy duty
[Us] Rated Supply Voltage
380...480 V - 15...10 %
Mounting Mode
wall mount
Emc Filter
class C3 EMC filter integrated

Offer Sustainability

Mercury Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Upgradeability
Upgraded components available
Rohs Exemption Information
Yes
Environmental Disclosure
ENVPEP1411001EN
Sustainable Offer Status
Green Premium product
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Circularity Profile
ENVEOLI1411001EN
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Environment

Product Certifications
UL || CSA || TÜV || EAC || CTick
Maximum Deflection Under Vibratory Load (During Operation)
1.5 mm at 2...13 Hz
Standards
IEC 61800-3 || IEC 61800-5-1 || IEC 60721-3 || IEC 61508 || IEC 13849-1 || UL 618000-5-1 || UL 508C || IEC 61000-3-12
Regulation Loop
adjustable PID regulator
Permitted Relative Humidity (During Operation)
class 3K5 according to EN 60721-3
Operating Altitude
<= 4800 m with current derating above 1000m
Overvoltage Category
class III
Environmental Class (During Operation)
class 3C3 according to IEC 60721-3-3 || class 3S3 according to IEC 60721-3-3
Maximum Acceleration Under Shock Impact (During Operation)
150 m/s² at 11 ms
Pollution Degree
2
Electromagnetic Compatibility
electrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5 || conducted radio-frequency immunity test level 3 IEC 61000-4-6
Ambient Air Temperature For Operation
-15-50 °C without derating vertical position) || 50-60 °C with derating factor vertical position)
Volume Of Cooling Air
240.0 m3/h
Marking
CE
Maximum Acceleration Under Vibrational Stress (During Operation)
10 m/s² at 13...200 Hz
Noise Level
63.5 dB
Ambient Air Temperature For Storage
-40-70 °C
Type Of Cooling
forced convection
Isolation
between power and control terminals
Assembly Style
with heat sink
Operating Position
vertical +/- 10 degree
Maximum Thdi
<48 % full load IEC 61000-3-12 || <48 % 80 % load IEC 61000-3-12
Ambient Air Transport Temperature
-40-70 °C

Documents

Data Sheet

Download

CAD Models

Trace parts
Trace parts
Download

Related products