Schneider Electric

ATV650D55N4EU

variable speed drive, Altivar Process ATV600, ATV650, 55kW, 400...480V, IP55
ATV650D55N4EU
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
€4,154.95

Additional Information

Part Number
ATV650D55N4EU
UNSPSC
39122001
Tariff Code
8504404000
Country of Origin
CN

Complementary

Discrete Input Logic
positive logic (source) DI1...DI8), < 5 V, > 11 V || negative logic (sink) DI1...DI8), > 16 V, < 10 V
Analogue Output Type
software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 10 bits || software-configurable current DQ-, DQ+ 30 V DC || software-configurable current DQ-, DQ+ 100 mA
Discrete Output Type
relay outputs R1A, R1B, R1C 250 V AC 3000 mA || relay outputs R1A, R1B, R1C 30 V DC 3000 mA || relay outputs R2A, R2C 250 V AC 5000 mA || relay outputs R2A, R2C 30 V DC 5000 mA || relay outputs R3A, R3C 250 V AC 5000 mA || relay outputs R3A, R3C 30 V DC 5000 mA
Maximum Switching Current
relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC || relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC
Exchange Mode
half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Phase
3 phase
Net Weight
87 kg
Type Of Polarization
no impedance
Frequency Resolution
analog input 0.012/50 Hz || display unit 0.1 Hz
Relay Output Type
configurable relay logic R2 sequence relay NO 100000 cycles || configurable relay logic R3 sequence relay NO 100000 cycles || configurable relay logic R1 fault relay NO/NC 100000 cycles
Maximum Transient Current
132 A 60 s heavy duty) || 116.6 A 60 s normal duty)
Analogue Input Number
3
Motor Slip Compensation
automatic whatever the load || not available in permanent magnet motor law || can be suppressed
Discrete Output Number
0
Method Of Access
slave Modbus TCP
Discrete Input Number
8
Local Signalling
for embedded communication status 3 LEDs (dual colour) || for communication module status 4 LEDs (dual colour) || for presence of voltage 1 LED (red) || for local diagnostic 3 LEDs
Linearity Error
AO1, AO2 +/- 0.2 % analog output || AI1, AI2, AI3 +/- 0.15 % of maximum value analog input
Number Of Addresses
1-247 Modbus serial
Width
345 mm
Transmission Rate
10, 100 Mbits || 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
Depth
436 mm
Analogue Input Type
AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits || AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits
Sampling Duration
5 ms +/- 1 ms DI5, DI6) - discrete input || 5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input || 10 ms +/- 1 ms AO1) - analog output || 2 ms +/- 0.5 ms DI1...DI4) - discrete input
Electrical Connection
line side screw terminal 70...95 mm² || motor screw terminal 70...120 mm² || control removable screw terminals 0.5...1.5 mm²
Maximum Output Frequency
500 kHz
Height
1250 mm
Acceleration And Deceleration Ramps
linear adjustable separately from 0.01...9999 s
Transmission Frame
RTU
Relay Output Number
3
Data Format
8 bits, configurable odd, even or no parity
Accuracy
+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output || +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
Connector Type
RJ45 on the remote graphic terminal)Modbus serial || RJ45 on the remote graphic terminal)Ethernet/Modbus TCP
Input Compatibility
DI5, DI6 discrete input level 1 PLC IEC 65A-68 || STOA, STOB discrete input level 1 PLC IEC 61131-2 || DI1...DI6 discrete input level 1 PLC IEC 61131-2
Permissible Temporary Current Boost
1.5 x In 60 s heavy duty) || 1.1 x In 60 s normal duty)
Mounting Mode
wall mount
Analogue Output Number
2
Physical Interface
Ethernet || 2-wire RS 485
Minimum Switching Current
relay output R1, R2, R3 5 mA 24 V DC
Refresh Time
relay output R1, R2, R3)5 ms +/- 0.5 ms)
Enclosure Mounting
wall mounted
Isolation
between power and control terminals
Output Voltage
<= power supply voltage
Quantity Per Set
1
Braking To Standstill
by DC injection
Discrete Input Type
DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V)
Protection Type
safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-circuit protection drive || motor phase break drive || overvoltages on the DC bus drive || line supply overvoltage drive || line supply undervoltage drive || line supply phase loss drive || overspeed drive || break on the control circuit drive || thermal protection motor
Supply
internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for digital inputs and STO 24 V DC 21-27 V), <200 mA overload and short-circuit protection || external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection

Specifications

Prospective Line Isc
50 kA
Product Destination
asynchronous motors || synchronous motors
Line Current
84.2 A 480 V normal duty) || 81.4 A 380 V heavy duty) || 71.8 A 480 V heavy duty) || 97.2 A 380 V normal duty)
Emc Filter
integrated 150 m IEC 61800-3 category C3
Asynchronous Motor Control Profile
variable torque standard || optimized torque mode
Variant
with disconnect switch
Product Or Component Type
variable speed drive
Apparent Power
59.7 kVA 480 V heavy duty) || 70 kVA 480 V normal duty)
Switching Frequency
2...8 kHz adjustable || 2.5...8 kHz with derating factor
Communication Port Protocol
Modbus serial || Ethernet
Product Specific Application
process and utilities
Safety Function
STO (safe torque off) SIL 3
Maximum Horse Power Rating
60 hp heavy duty || 75 hp normal duty
Supply Frequency
50...60 Hz - 5...5 %
Option Card
slot A communication module, PROFINET || slot A communication module, DeviceNet || slot A communication module, Modbus TCP/EtherNet/IP || slot A communication module, CANopen daisy chain RJ45 || slot A communication module, CANopen SUB-D 9 || slot A communication module, CANopen screw terminals || slot A/slot B digital and analog I/O extension module || slot A/slot B output relay extension module || slot A communication module, Ethernet IP/Modbus TCP/MD-Link || communication module, BACnet MS/TP || communication module, Ethernet Powerlink || slot A communication module, Profibus DP V1
Degree Of Protection
UL type 12 UL 508C
Range Of Product
Altivar Process ATV600
Speed Drive Output Frequency
0.1-500 Hz
Ip Degree Of Protection
IP55IEC 60529 || IP55IEC 61800-5-1
Motor Power Kw
45 kW heavy duty) || 55 kW normal duty)
[Us] Rated Supply Voltage
380...480 V
[Us] Rated Supply Voltage
380...480 V - 15...10 %
Discrete Input Logic
16 preset speeds
Type Of Cooling
forced convection
Continuous Output Current
87 A 2.5 kHz heavy duty || 106 A 2.5 kHz normal duty
Nominal Switching Frequency
2.5 kHz
Device Short Name
ATV650
Synchronous Motor Control Profile
synchronous reluctance motor || permanent magnet motor

Environment

Product Certifications
ATEX INERIS || ATEX zone 2/22 || TÜV || UL || DNV-GL || CSA
Standards
IEC 61800-3 environment 1 category C2 || EN/IEC 61800-3 environment 2 category C3 || IEC 61800-5-1 || IEC 61000-3-12 || IEC 60721-3 || IEC 61508 || IEC 13849-1 || IEC 61800-3
Insulation Resistance
> 1 MOhm 500 V DC for 1 minute to earth
Shock Resistance
15 gn 11 ms IEC 60068-2-27
Vibration Resistance
1 gn 13-200 Hz)IEC 60068-2-6 || 1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6
Noise Level
69.9 dB 86/188/EEC
Regulation Loop
adjustable PID regulator
Operating Altitude
1000...4800 m with current derating 1 % per 100 m || <= 3280.84 ft (1000 m) without derating
Overvoltage Category
III
Pollution Degree
3
Electromagnetic Compatibility
radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5 || conducted radio-frequency immunity test level 3 IEC 61000-4-6 || electrostatic discharge immunity test level 3 IEC 61000-4-2
Ambient Air Temperature For Operation
40-50 °C with derating factor) || -15-40 °C without derating)
Marking
CE
Pollution Degree
2 IEC 61800-5-1
Noise Level
69.9 dB
Ambient Air Temperature For Storage
-40-70 °C
Relative Humidity
5-95 % without condensation IEC 60068-2-3
Operating Position
vertical +/- 10 degree
Maximum Thdi
<48 % from 80...100 % of load IEC 61000-3-12

Offer Sustainability

Mercury Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Upgradeability
Upgraded components available
Rohs Exemption Information
Yes
Environmental Disclosure
ENVPEP1506002EN
Sustainable Offer Status
Green Premium product
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Circularity Profile
ENVEOLI1506002EN
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Documents

Data Sheet

Download

CAD Models

Trace parts
Trace parts
Download

Related products