Schneider Electric
BDA160403
Circuit breaker, PowerPacT B, 40A, 1 pole, 600Y/347VAC, 14kA, I-Line, thermal magnetic, 80%, B
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Additional Information
- Part Number
- BDA160403
- UNSPSC
- 39121601
- Tariff Code
- 8536200020
- Country of Origin
- MX
Complementary
- Mounting Mode
- I-Line
- Network Frequency
- 50/60 Hz
- [Ics] Rated Service Breaking Capacity
- 25 kA 220...240 V AC 50/60 Hz IEC 60947-2
- Trip Unit Technology
- thermal-magnetic
- Height
- 137 mm
- Connection Pitch
- 27 mm
- [Ue] Rated Operational Voltage
- 240 V AC 50/60 Hz UL 489
- Tightening Torque
- 3.6-4.4 N.m 2.5-6 mm² (AWG 14...AWG 10) || 5-6.2 N.m 10-70 mm² (AWG 8...AWG 2/0)
- Breaking Capacity Code
- D
- 9 Mm Pitches
- 3
- Local Signalling
- presence of auxiliary contacts flag green)
- Electrical Connection
- I-Line connection, line || lugs, load
- Mounting Height
- 38.1 mm
- Net Weight
- 0.6375 kg
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV IEC 60947-2
- Control Type
- toggle
- Circuit Breaker Application
- HACR rated
- Wire Stripping Length
- 20 mm
- Utilisation Category
- category A
- Line Rated Current
- 40-40 A
- Continuous Current Rating
- 80 %
- Breaking Capacity
- 25 kA 208Y/120 V AC 50/60 Hz UL 489 || 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480Y/277 V AC 50/60 Hz UL 489 || 14 kA 125 V DC 50/60 Hz UL 489 || 10 kA 600/347 V AC 50/60 Hz UL 489
- [Ui] Rated Insulation Voltage
- 800 V IEC 60947-2
- Mechanical Durability
- 20000 cycles IEC 947-1 Annex K ed 5.2
- Suitability For Isolation
- yes IEC 60947-2
- Electrical Durability
- 10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
- Poles Description
- 1P
- Quantity Per Set
- set of 1
- Awg Gauge
- AWG 14...AWG 2/0 aluminium/copper
- Color
- Gray RAL 7016)
- Width
- 27 mm
- Depth
- 89 mm
- Phase Connection
- B
Environment
- Ik Degree Of Protection
- IK07 IEC 62262
- Ambient Air Temperature For Operation
- -25-70 °C
- Standards
- UL 489 || EN/IEC 60947-5-1 || EN/IEC 60947-2 || CSA C22.2 No 5 || GB 14048.2 || NEMA AB1 || NMX J-266
- Product Certifications
- UL || IEC || CCC || EAC || CSA || NOM
- Ip Degree Of Protection
- front cover IP40 IEC 60529
- Pollution Degree
- 3 IEC 60947-1
- Ambient Air Temperature For Storage
- -50-85 °C
- Quality Labels
- CE
- Operating Altitude
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1610005EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Eu Rohs Directive
- Compliant
- Halogen Content Performance
- Halogen free product
Specifications
- Product Or Component Type
- circuit breaker
- Product Name
- PowerPact B
- Range
- PowerPact
- Device Application
- distribution
- Device Short Name
- BD 040
Documents
Data Sheet
DownloadOther Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther