Circuit breaker, PowerPacT B, 125A, 1 pole, 600Y/347VAC, 14kA, terminal nut, thermal magnetic, 80%
BDF16125
BDF16125
BDF16125
BDF16125
BDF16125
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1610005EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
California Proposition 65
WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Eu Rohs Directive
Compliant
Halogen Content Performance
Halogen free product

Complementary

Mounting Mode
clip-on 35 mm symmetrical DIN rail) || by screws plate)
Network Frequency
50/60 Hz
[Ics] Rated Service Breaking Capacity
25 kA 220...240 V AC 50/60 Hz IEC 60947-2
Trip Unit Technology
thermal-magneticTM-D,
Trip Unit Name
TM-D
Height
137 mm
Connection Pitch
27 mm
[Ue] Rated Operational Voltage
240 V AC 50/60 Hz UL 489
Tightening Torque
5-5 N.m 2.5-16 mm² (AWG 14...AWG 4) || 9-9 N.m 25-95 mm² (AWG 3...AWG 3/0)
Breaking Capacity Code
D
9 Mm Pitches
3
Protected Poles Description
1t
Electrical Connection
terminal nut, ON and OFF end
Net Weight
0.46 kg
[Uimp] Rated Impulse Withstand Voltage
8 kV IEC 60947-2
Control Type
toggle
Circuit Breaker Application
HACR rated
Wire Stripping Length
20 mm
Utilisation Category
category A
Line Rated Current
125-125 A
Continuous Current Rating
80 %
Breaking Capacity
25 kA 208Y/120 V AC 50/60 Hz UL 489 || 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480Y/277 V AC 50/60 Hz UL 489 || 10 kA 125 V DC 50/60 Hz UL 489 || 14 kA 600/347 V AC 50/60 Hz UL 489
[Ui] Rated Insulation Voltage
800 V IEC 60947-2
Mechanical Durability
15000 cycles IEC 947-1 Annex F ed 5.2
Suitability For Isolation
yes IEC 60947-2
Electrical Durability
10000 cycles IEC 947-1 Annex K ed 5.2 In
Poles Description
1P
Quantity Per Set
set of 1
Awg Gauge
AWG 14...AWG 8 aluminium/copper || AWG 6...AWG 3/0 aluminium/copper
Color
Gray RAL 7016)
Width
27 mm
Depth
80 mm

Environment

Ik Degree Of Protection
IK07 IEC 62262
Ambient Air Temperature For Operation
-25-70 °C
Standards
GB 14048.2 || UL 489 || NMX J-266 || NEMA AB1 || EN/IEC 60947-5-1 || EN/IEC 60947-2 || CSA C22.2 No 5
Product Certifications
UL || IEC || CCC || EAC || CSA || NOM
Ip Degree Of Protection
front cover IP40 IEC 60529
Pollution Degree
3 IEC 60947-1
Ambient Air Temperature For Storage
-50-85 °C
Quality Labels
CE
Operating Altitude
6561.68 ft (2000 m) without derating || 5000 m with derating

Specifications

Product Or Component Type
circuit breaker
Product Name
PowerPact B
Range
PowerPact
Device Application
distribution
Device Short Name
BD 125

Documents

Data Sheet

Download