analog ouput module X80 - 4 outputs HART - current Isolated - for severe environment
BMEAHO0412C
BMEAHO0412C
BMEAHO0412C
BMEAHO0412C
BMEAHO0412C
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
€582.45

Additional Information

Part Number
BMEAHO0412C
UNSPSC
32151705
Tariff Code
8538908180

Environment

Ambient Air Temperature For Operation
-25-60 °C
Directives
2014/35/EU - low voltage directive || 2014/30/EU - electromagnetic compatibility || 2014/34/EU - ATEX directive
Ambient Air Temperature For Storage
-40-85 °C
Standards
EN/IEC 61131-2 || EN/IEC 61010-2-201 || UL 61010-2-201 || CSA C22.2 No 61010-2-201 || IACS E10 || EN/IEC 61000-6-5, interface type 1 and type 2 || EN/IEC 61850-3, location G || EN/IEC 60079-0
Product Certifications
CE || UL || CSA || RCM || EAC || Merchant Navy || ATEX zone 2/22 || IECEx zone 2/22
Operating Altitude
0...6561.68 ft (0...2000 m) || 2000...5000 m with derating factor
Environmental Characteristic
gas resistant class Gx ISA S71.04 || gas resistant class 3C4 IEC 60721-3-3 || dust resistant class 3S4 IEC 60721-3-3 || sand resistant class 3S4 IEC 60721-3-3 || salt resistant level 2 IEC 68252 || mold growth resistant class 3B2 IEC 60721-3-3 || fungal spore resistant class 3B2 IEC 60721-3-3 || hazardous location class I division 2
Protective Treatment
conformal coating

Specifications

Range Of Product
Modicon X80
Product Or Component Type
analog output module

Offer Sustainability

China Rohs Regulation
X
Rohs Exemption Information
Yes
Mercury Free
Yes
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.

Complementary

Topology
point-to-point
Input Output Isolation
isolated
Isolation Voltage
1000 V DC 60 s between channels || 1400 V DC 60 s between channels and ground || 1400 V DC 60 s between channels and bus
Function Available
I/O mapping
Analogue Output Number
4
Load Impedance Ohmic
600 Ohm 0...20 mA || 570 Ohm 0...21 mA
Measurement Error
0.1 % of full scale 25 °C || 0.45 % of full scale - 25...60 °C
Application Specific I/O
HART
Temperature Drift
45 ppm/°C
Analogue Output Type
current 4...20 mA
Analogue Output Resolution
15 bits + sign
Product Compatibility
BMEP58... processor || BMEXBP... backplane || ABE7CPA21 || head module BMECRA31210 || BMXFTB20... terminal block
Net Weight
0.223 kg
Electrical Connection
20 ways terminal block || Telefast
Checks
broken wire detection

Documents

Data Sheet

Download