Schneider Electric
BMEAHO0412C
analog ouput module X80 - 4 outputs HART - current Isolated - for severe environment
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Product Conditions:
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
€582.45
Additional Information
- Part Number
- BMEAHO0412C
- UNSPSC
- 32151705
- Tariff Code
- 8538908180
Environment
- Ambient Air Temperature For Operation
- -25-60 °C
- Directives
- 2014/35/EU - low voltage directive || 2014/30/EU - electromagnetic compatibility || 2014/34/EU - ATEX directive
- Ambient Air Temperature For Storage
- -40-85 °C
- Standards
- EN/IEC 61131-2 || EN/IEC 61010-2-201 || UL 61010-2-201 || CSA C22.2 No 61010-2-201 || IACS E10 || EN/IEC 61000-6-5, interface type 1 and type 2 || EN/IEC 61850-3, location G || EN/IEC 60079-0
- Product Certifications
- CE || UL || CSA || RCM || EAC || Merchant Navy || ATEX zone 2/22 || IECEx zone 2/22
- Operating Altitude
- 0...6561.68 ft (0...2000 m) || 2000...5000 m with derating factor
- Environmental Characteristic
- gas resistant class Gx ISA S71.04 || gas resistant class 3C4 IEC 60721-3-3 || dust resistant class 3S4 IEC 60721-3-3 || sand resistant class 3S4 IEC 60721-3-3 || salt resistant level 2 IEC 68252 || mold growth resistant class 3B2 IEC 60721-3-3 || fungal spore resistant class 3B2 IEC 60721-3-3 || hazardous location class I division 2
- Protective Treatment
- conformal coating
Specifications
- Range Of Product
- Modicon X80
- Product Or Component Type
- analog output module
Offer Sustainability
- China Rohs Regulation
- X
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Eu Rohs Directive
- Pro-active compliance (Product out of EU RoHS legal scope)
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Complementary
- Topology
- point-to-point
- Input Output Isolation
- isolated
- Isolation Voltage
- 1000 V DC 60 s between channels || 1400 V DC 60 s between channels and ground || 1400 V DC 60 s between channels and bus
- Function Available
- I/O mapping
- Analogue Output Number
- 4
- Load Impedance Ohmic
- 600 Ohm 0...20 mA || 570 Ohm 0...21 mA
- Measurement Error
- 0.1 % of full scale 25 °C || 0.45 % of full scale - 25...60 °C
- Application Specific I/O
- HART
- Temperature Drift
- 45 ppm/°C
- Analogue Output Type
- current 4...20 mA
- Analogue Output Resolution
- 15 bits + sign
- Product Compatibility
- BMEP58... processor || BMEXBP... backplane || ABE7CPA21 || head module BMECRA31210 || BMXFTB20... terminal block
- Net Weight
- 0.223 kg
- Electrical Connection
- 20 ways terminal block || Telefast
- Checks
- broken wire detection
Documents
Data Sheet
DownloadOther Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther