discrete output module, Modicon X80, 16 NO relay outputs, 24 to 240V AC, 24 to 48V DC
BMXDRA1605
BMXDRA1605
BMXDRA1605
BMXDRA1605
BMXDRA1605
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
$216.97
1
Payment methods:
A total of 293 Parts In-Stock from 47 Distributors

Additional Information

Part Number
BMXDRA1605
UNSPSC
32151706
Tariff Code
8538908180
Country of Origin
FR

Environment

Ambient Air Temperature For Operation
0-60 °C
Shock Resistance
30 gn
Dielectric Strength
2000 V AC 50/60 Hz 1 min
Vibration Resistance
3 gn
Ambient Air Temperature For Storage
-40-85 °C
Relative Humidity
5-95 % 55-55 °C without condensation
Operating Altitude
0...6561.68 ft (0...2000 m) || 2000...5000 m with derating factor
Ip Degree Of Protection
IP20

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Complementary

Mtbf Reliability
2100000 H
Minimum Switching Current
1 mA 5 V DC
Status Led
1 LED (Green) RUN || 1 LED per channel (Green) channel diagnostic || 1 LED (Red) ERR || 1 LED (Red) I/O
Insulation Resistance
> 10 MOhm 500 V DC
[Ith] Conventional Free Air Thermal Current
2 A
Power Dissipation In W
3 W
Net Weight
0.15 kg
Electrical Durability
AC-15 100000 cycles 240 VA 200 V 0.7 ) || AC-15 100000 cycles 120 VA 200 V 0.35 ) || AC-12 100000 cycles 200 VA 100 V || AC-12 100000 cycles 80 VA 48 V || AC-12 100000 cycles 50 VA 24 V || AC-15 100000 cycles 120 VA 100 V || AC-15 100000 cycles 120 VA 24 V || AC-15 100000 cycles 120 VA 48 V || DC-12 100000 cycles 24 W 24 V || DC-13 100000 cycles 10 W 24 V || DC-13 100000 cycles 10 W 48 V || AC-15 300000 cycles 72 VA 200 V 0.7 ) || AC-15 300000 cycles 36 VA 200 V 0.35 ) || AC-12 300000 cycles 200 VA 200 V || AC-12 300000 cycles 80 VA 100 V || AC-12 300000 cycles 50 VA 48 V || AC-15 300000 cycles 36 VA 100 V || AC-15 300000 cycles 72 VA 100 V || AC-15 300000 cycles 36 VA 48 V || AC-15 300000 cycles 72 VA 48 V || AC-15 300000 cycles 36 VA 24 V || AC-15 300000 cycles 72 VA 24 V || DC-13 300000 cycles 3 W 24 V || DC-13 300000 cycles 3 W 48 V || DC-13 7000 cycles 24 W 24 V || DC-13 7000 cycles 24 W 48 V || DC-12 50000 cycles 24 W 48 V
Typical Current Consumption
100 mA 3.3 V DC || 95 mA 24 V DC
Output Overvoltage Protection
use discharge diode on each output DC || use RC circuit on each output AC || use ZNO surge limiter on each output AC
Output Short-Circuit Protection
use 1 fast blow fuse per channel or group of channel
Output Overload Protection
use 1 fast blow fuse per channel or group of channel
Response Time On Output
< 8 ms activation || < 10 ms deactivation

Specifications

Discrete Output Type
relay
Range Of Product
Modicon X80
Discrete Output Number
16 EN/IEC 61131-2
Discrete Output Voltage
24...48 V 19...60 V DC || 24...240 V 19…264 V AC
Product Or Component Type
discrete output module

Documents

Data Sheet

Download

CAD Models

Trace parts
Trace parts