Specifications

[Uc] Control Circuit Voltage
120 V AC 60 Hz
Auxiliary Contact Composition
1 NO
Contactor Application
motor control || resistive load
Product Or Component Type
contactor
Product Name
Easy TeSys DPE
Range
Easy TeSys
Pole Contact Composition
3 NO
Utilisation Category
AC-1 || AC-3
[Ie] Rated Operational Current
60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit || 40 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
Poles Description
3P
Maximum Horse Power Rating
3 hp at 115 V AC 50/60 Hz for 1 phase motors || 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 7.5 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 7.5 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 30 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 25 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Motor Power Kw
11 kW 220...230 V AC 50/60 Hz || 18.5 kW 380...400 V AC 50/60 Hz || 22 kW 415...440 V AC 50/60 Hz || 22 kW 500 V AC 50/60 Hz || 30 kW 660...690 V AC 50/60 Hz
Device Short Name
DPE

Complementary

Minimum Switching Current
5 mA for signalling circuit
[Ue] Rated Operational Voltage
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Height
122 mm
Power Dissipation Per Pole
2.4 W AC-3 || 5.4 W AC-1
Average Impedance
1.5 mOhm - Ith 60 A 50 Hz for power circuit
Control Circuit Voltage Limits
drop-out: 0.3...0.6 Uc at 60 Hz (at <70 °C) || operational: 0.85...1.1 Uc at 60 Hz (at <60 °C) || operational: 1...1.1 Uc at 60 Hz (at <70 °C)
[Ith] Conventional Free Air Thermal Current
10 A (at 60 °C) for signalling circuit || 60 A (at 60 °C) for power circuit
Mounting Support
rail || plate
Control Circuit Type
AC 60 Hz
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Insulation Resistance
> 10 MOhm for signalling circuit
Rated Breaking Capacity
800 A at 440 V for power circuit conforming to IEC 60947
Irms Rated Making Capacity
140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1 || 800 A at 440 V for power circuit conforming to IEC 60947
Associated Fuse Rating
10 A gG for signalling circuit conforming to IEC 60947-5-1 || 80 A gG at <= 690 V coordination type 1 for power circuit || 80 A gG at <= 690 V coordination type 2 for power circuit
Net Weight
0.89 kg
Inrush Power In Va
140-140 VA 60 Hz cos phi 0.75 (at 20 °C)
Connections - Terminals
power circuit: screw connection 1 2.5-25 mm² - cable stiffness: flexible without cable end || power circuit: screw connection 2 2.5-16 mm² - cable stiffness: flexible without cable end || power circuit: screw connection 1 2.5-25 mm² - cable stiffness: flexible with cable end || power circuit: screw connection 2 2.5-10 mm² - cable stiffness: flexible with cable end || power circuit: screw connection 1 2.5-25 mm² - cable stiffness: solid without cable end || power circuit: screw connection 2 2.5-16 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end
Coil Technology
without built-in suppressor module
Minimum Switching Voltage
17 V for signalling circuit
Maximum Operating Rate
3600 cyc/h 60 °C
Signalling Circuit Frequency
25...400 Hz
Tightening Torque
power circuit 7 N.m screw connectors 16-25 mm² hexagonal 4 mm || power circuit 5 N.m screw connectors 2.5-16 mm² hexagonal 4 mm || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2
Electrical Durability
0.6 Mcycles 60 A AC-1 <= 440 V || 1 Mcycles 40 A AC-3 <= 440 V
Mechanical Durability
5 Mcycles
Auxiliary Contacts Type
mechanically linked 1 NO IEC 60947-5-1
Hold-In Power Consumption In Va
13-13 VA 60 Hz cos phi 0.3 (at 20 °C)
Operating Time
4...19 ms opening || 12...26 ms closing
Width
55 mm
Depth
122 mm
[Icw] Rated Short-Time Withstand Current
320 A 40 °C - 10 s for power circuit || 720 A 40 °C - 1 s for power circuit || 72 A 40 °C - 10 min for power circuit || 165 A 40 °C - 1 min for power circuit || 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit
Heat Dissipation
4-5 W 60 Hz

Environment

Product Certifications
cULus
Ambient Air Temperature For Operation
-40-60 °C
Standards
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 60947-4-1
Climatic Withstand
IACS E10 || IEC 60947-1 Annex Q category D
Pollution Degree
3
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947
Ambient Air Temperature For Storage
-60-80 °C
Ip Degree Of Protection
IP20 front face IEC 60529
Mechanical Robustness
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
Operating Altitude
0...6561.68 ft (0...2000 m)
Fire Resistance
850 °C IEC 60695-2-1
Overvoltage Category
III
[Ui] Rated Insulation Voltage
power circuit 690 V IEC 60947-4-1 || power circuit 600 V cUL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V cUL

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1503009EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
ENVEOLI1503009EN
Eu Rohs Directive
Compliant