IEC contactor,Easy TeSys DPE,nonreversing,50A,3P,30HP at 480V AC,24VDC coil
DPE50BD
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Complementary

Minimum Switching Current
5 mA for signalling circuit
[Ue] Rated Operational Voltage
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Height
122 mm
Power Dissipation Per Pole
3.7 W AC-3 || 9.6 W AC-1
Average Impedance
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Control Circuit Voltage Limits
drop-out: 0.1...0.3 Uc (at <60 °C) || operational: 0.75...1.25 Uc (at <60 °C)
[Ith] Conventional Free Air Thermal Current
10 A (at 60 °C) for signalling circuit || 60 A (at 60 °C) for power circuit
Mounting Support
rail || plate
Control Circuit Type
DC 50/60 Hz
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Hold-In Power Consumption In W
7.4-7.4 W 20 °C
Insulation Resistance
> 10 MOhm for signalling circuit
Rated Breaking Capacity
800 A at 440 V for power circuit conforming to IEC 60947
Irms Rated Making Capacity
140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1 || 800 A at 440 V for power circuit conforming to IEC 60947
Associated Fuse Rating
10 A gG for signalling circuit conforming to IEC 60947-5-1 || 100 A gG at <= 690 V coordination type 1 for power circuit || 100 A gG at <= 690 V coordination type 2 for power circuit
Connections - Terminals
power circuit: screw connection 1 2.5-25 mm² - cable stiffness: flexible without cable end || power circuit: screw connection 2 2.5-16 mm² - cable stiffness: flexible without cable end || power circuit: screw connection 1 2.5-25 mm² - cable stiffness: flexible with cable end || power circuit: screw connection 2 2.5-10 mm² - cable stiffness: flexible with cable end || power circuit: screw connection 1 2.5-25 mm² - cable stiffness: solid without cable end || power circuit: screw connection 2 2.5-16 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end
Coil Technology
without built-in suppressor module
Minimum Switching Voltage
17 V for signalling circuit
Maximum Operating Rate
3600 cyc/h 60 °C
Signalling Circuit Frequency
25...400 Hz
Tightening Torque
power circuit 7 N.m screw connectors 16-25 mm² hexagonal 4 mm || power circuit 5 N.m screw connectors 2.5-16 mm² hexagonal 4 mm || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2
Electrical Durability
0.6 Mcycles 60 A AC-1 <= 440 V || 1 Mcycles 40 A AC-3 <= 440 V
Mechanical Durability
5 Mcycles
Inrush Power In W
19-19 W 20 °C)
Auxiliary Contacts Type
mechanically linked 1 NO IEC 60947-5-1
Operating Time
4...19 ms opening || 12...26 ms closing
Width
55 mm
Depth
122 mm
[Icw] Rated Short-Time Withstand Current
400 A 40 °C - 10 s for power circuit || 810 A 40 °C - 1 s for power circuit || 84 A 40 °C - 10 min for power circuit || 208 A 40 °C - 1 min for power circuit || 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit
Heat Dissipation
4-5 W 50/60 Hz

Environment

Product Certifications
cULus
Ambient Air Temperature For Operation
-40-60 °C
Standards
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 60947-4-1
Climatic Withstand
IACS E10 || IEC 60947-1 Annex Q category D
Pollution Degree
3
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947
Ambient Air Temperature For Storage
-60-80 °C
Ip Degree Of Protection
IP20 front face IEC 60529
Mechanical Robustness
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
Operating Altitude
0...6561.68 ft (0...2000 m)
Fire Resistance
850 °C IEC 60695-2-1
Overvoltage Category
III
[Ui] Rated Insulation Voltage
power circuit 690 V IEC 60947-4-1 || power circuit 600 V cUL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V cUL

Specifications

[Uc] Control Circuit Voltage
24 V DC
Auxiliary Contact Composition
1 NO
Contactor Application
motor control || resistive load
Product Or Component Type
contactor
Product Name
Easy TeSys DPE
Range
Easy TeSys
Pole Contact Composition
3 NO
Utilisation Category
AC-1 || AC-3
[Ie] Rated Operational Current
80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit || 50 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
Poles Description
3P
Maximum Horse Power Rating
3 hp at 115 V AC 50/60 Hz for 1 phase motors || 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 10 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 10 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 30 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 30 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Motor Power Kw
15 kW 220...230 V AC 50/60 Hz || 22 kW 380...400 V AC 50/60 Hz || 25 kW 415 V AC 50/60 Hz || 30 kW 440 V AC 50/60 Hz || 30 kW 500 V AC 50/60 Hz || 33 kW 660...690 V AC 50/60 Hz
Device Short Name
DPE

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1503009EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI1503009EN
Eu Rohs Directive
Compliant with Exemptions

Documents

Data Sheet

Download

Related products