Transformer, dry type, DOE 2016, 500kVA, 3 phase, 600V delta primary, 208Y/120V secondary, 30J, 150C rise
EX500T79H
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1604028EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
N/A
Eu Rohs Directive
Compliant
Halogen Content Performance
Halogen free plastic parts product

Complementary

Network Frequency
60 Hz
Primary Voltage
600 V delta
Height
1803 mm
[Uimp] Rated Impulse Withstand Voltage
10 kV
Temperature Rise
150 °C || 220 °C insulated
Degree Of Protection
UL type 1 || UL type 2, with 7400DS30J || UL type 3R, with 7400WS30J
Number Of Tap-Offs
2 2.5 % FCAN || 2 2.5 % FCBN
Rated Operational Power In Va
500 kVA
Electrical Connection
4 Hole Nema Pad primary 11.1 mm || 6 Hole Nema Pad secondary 11.1 mm || 8 Hole Nema Pad sec - XO 11.1 mm
Phase
3 phase
Material
aluminium
Net Weight
1322.22 kg
Secondary Voltage
208Y/120 V
Noise Level
6 dB NEMA ST-20 || 56 dB
Type Of Cooling
natural convection
Mounting Support
floor || floor, with 7400FMB
Width
1226 mm
Depth
963 mm
Box Number
30J

Specifications

Range Of Product
Square D
Product Or Component Type
transformer
Transformer Type
energy efficient
Device Application
low voltage electrical distribution
Device Short Name
DOE 2016

Environment

Average Ambient Air Temperature For Operation
30 °C
Ambient Air Temperature For Operation
40-40 °C
Standards
UL 1561 || CSA C22.2 No 47 || NEMA ST-20