EXN150T6H

Transformer, dry type, DOE 2016, 150kVA, 3 phase, 480V delta primary, 240V delta secondary, 22M, 150C rise
EXN150T6H
EXN150T6H
EXN150T6H
EXN150T6H
EXN150T6H
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up

Complementary

Tap Loss
306 no load (core loss) || 2721 load loss (coil loss)
Network Frequency
60 Hz
Primary Voltage
480 V delta
Percentage Impedance Voltage
3.08 %
Height
1031 mm
Number Of Mounting Holes
4 Ø: 13 mm
[Uimp] Rated Impulse Withstand Voltage
10 kV
Primary Operational Current
180.42-180.42 A 360.84 A 150 kVA
Temperature Rise
150 °C || 220 °C insulated
Degree Of Protection
UL type 2 || UL type 3R, with 7400WS22M
Number Of Tap-Offs
2 2.5 % FCAN || 4 2.5 % FCBN
X/R Ratio
1.66
Rated Operational Power In Va
150 kVA
Electrical Connection
4 Hole Nema Pad secondary 11.1 mm || 2 Hole Nema Pad primary 11.1 mm
Phase
3 phase
Material
aluminium
Net Weight
456.77 kg
Secondary Voltage
240 V delta
Percentage Reactance
2.57 %
Noise Level
47 dB || 3 dB NEMA ST-20
Type Of Cooling
natural convection
Efficiency
98.91 % at 35 % load factor , 75.0 °C
Mounting Support
floor || floor, with 7400FMB || ceiling, with 7400CMB22M
Continuous Thermal Current Rating Factor
1302 16.6 % || 1624 25 % || 3365 50 % || 6267 75 % || 10329 100 %
Width
855 mm
Depth
827 mm
Inrush Current
2053 A
Box Number
22M
[Ipk] Rated Peak Withstand Current
11.72 kA

Environment

Average Ambient Air Temperature For Operation
30 °C
Ambient Air Temperature For Operation
40-40 °C
Standards
UL 1561 || CSA C22.2 No 47 || NEMA ST-20

Specifications

Range Of Product
Square D
Product Or Component Type
transformer
Transformer Type
energy efficient
Device Application
low voltage electrical distribution
Device Short Name
DOE 2016

Documents

Data Sheet

Download

Related products