Schneider Electric
GV2P14
TeSys Deca Manual Starter and Protector, thermal magnetic circuit protector, rotary handle, 6 to 10 A, screw clamp
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
$114.24
1
Payment methods:
A total of 1,119 Parts In-Stock from 43 Distributors
Product Conditions:
Offer with manufacturer lead time
Ships in:On Request
Best price:
€26.70
Additional Information
- Part Number
- GV2P14
- UNSPSC
- 39121521
- Tariff Code
- 8536200020
- Country of Origin
- TH
Environment
- Product Certifications
- CCC || UL || CSA || EAC || ATEX || LROS (Lloyds register of shipping) || BV || RINA || DNV-GL || UKCA
- Ik Degree Of Protection
- IK04
- Mechanical Robustness
- shocks 30 Gn for 11 ms || vibrations 5 Gn, 5...150 Hz
- Ambient Air Temperature For Operation
- -20-60 °C
- Standards
- EN/IEC 60947-2 || EN/IEC 60947-4-1
- Climatic Withstand
- IACS E10
- Ambient Air Temperature For Storage
- -40-80 °C
- Ip Degree Of Protection
- IP20 IEC 60529
- Operating Altitude
- 6561.68 ft (2000 m)
- Fire Resistance
- 960 °C IEC 60695-2-11
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Environmental Disclosure
- ENVPEP2211002
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI2211002
- Eu Rohs Directive
- Compliant with Exemptions
Complementary
- Line Rated Current
- 10 A
- [Ue] Rated Operational Voltage
- 690 V AC 50/60 Hz IEC 60947-2
- Height
- 89 mm
- Phase Failure Sensitivity
- yes IEC 60947-4-1
- Rated Duty
- continuous IEC 60947-4-1
- Network Type
- AC
- Magnetic Tripping Current
- 138-138 A
- [Ith] Conventional Free Air Thermal Current
- 10 A IEC 60947-4-1
- Motor Power Kw
- 3-3 kW 400/415 V AC 50/60 Hz || 5-5 kW 500 V AC 50/60 Hz || 5.5-5.5 kW 690 V AC 50/60 Hz
- Utilisation Category
- category A IEC 60947-2 || AC-3 IEC 60947-4-1 || AC-3e IEC 60947-4-1
- Fixing Mode
- 35 mm symmetrical DIN rail clipped || panel screwed with 2 x M4 screws)
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV IEC 60947-2
- [Ics] Rated Service Short-Circuit Breaking Capacity
- 100 % 230/240 V AC 50/60 Hz IEC 60947-2 || 100 % 400/415 V AC 50/60 Hz IEC 60947-2 || 100 % 440 V AC 50/60 Hz IEC 60947-2 || 100 % 500 V AC 50/60 Hz IEC 60947-2 || 100 % 690 V AC 50/60 Hz IEC 60947-2
- Control Type
- rotary handle
- Power Dissipation Per Pole
- 2.5 W
- Electrical Durability
- 100000 cycles AC-3 415 V In || 100000 cycles AC-3e 415 V In
- [Ui] Rated Insulation Voltage
- 690 V AC 50/60 Hz IEC 60947-2
- Breaking Capacity
- 100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 6 kA Icu 690 V AC 50/60 Hz IEC 60947-2
- Suitability For Isolation
- yes IEC 60947-1 § 7-1-6
- Thermal Protection Adjustment Range
- 6-10 A IEC 60947-4-1
- Tightening Torque
- 1.7 N.m screw clamp terminal
- Mechanical Durability
- 100000 cycles
- Poles Description
- 3P
- Color
- dark grey
- Width
- 45 mm
- Depth
- 97 mm
- Network Frequency
- 50/60 Hz IEC 60947-4-1
Specifications
- Product Or Component Type
- motor circuit breaker
- Product Name
- TeSys GV2 || TeSys Deca
- Range
- TeSys Deca
- Device Application
- motor protection
- Device Short Name
- GV2P
- Trip Unit Technology
- thermal-magnetic
Documents
Data Sheet
DownloadCAD Models
traceparts
Download