IEC contactor, TeSys D, nonreversing, 80A resistive, 4 pole, 4 NO, 120VAC 50/60Hz coil, open style
LC1D65004G7
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:

Environment

Product Certifications
RINA || CCC || UL || CSA || GL || DNV || LROS (Lloyds register of shipping) || BV || UKCA
Height
122 mm
Standards
EN/IEC 60947-5-1 || CSA C22.2 No 14 || UL 508 || EN/IEC 60947-4-1
Flame Retardance
V1 conforming to UL 94
Protective Treatment
THIEC 60068-2-30
Ip Degree Of Protection
IP2X VDE 0106
Mechanical Robustness
shocks contactor open 8 Gn for 11 ms) || shocks contactor closed 10 Gn for 11 ms) || vibrations contactor opened 2 Gn, 5...300 Hz) || vibrations contactor closed 3 Gn, 5...300 Hz)
Operating Altitude
9842.52 ft (3000 m) without derating
Fire Resistance
850 °C IEC 60695-2-1
Width
85 mm
Depth
130 mm
Permissible Ambient Air Temperature Around The Device
-5-60 °C || -40-70 °C at Uc

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP110205EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
N/A
Eu Rohs Directive
Compliant

Complementary

Non-Overlap Time
1.5 ms on de-energisation between NC and NO contacts || 1.5 ms on energisation between NC and NO contacts
Minimum Switching Current
5 mA for control circuit
Power Dissipation Per Pole
6.3 W AC-3 || 9.6 W AC-1
Average Impedance
1 mOhm - Ith 80 A 50 Hz for power circuit
[Ith] Conventional Free Air Thermal Current
10 A (at 60 °C) for control circuit || 80 A (at 60 °C) for power circuit
Control Circuit Voltage Limits
0.3...0.6 Uc 60-60 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc 60-60 °C operational AC 50/60 Hz
Mounting Support
rail || plate
Control Circuit Type
AC 50/60 Hz standard
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Insulation Resistance
> 10 MOhm for control circuit
Rated Breaking Capacity
1000 kA at 440 V for power circuit conforming to IEC 60947
Irms Rated Making Capacity
1000 A at 440 V AC for power circuit conforming to IEC 60947 || 140 A AC for control circuit conforming to IEC 60947-5-1
Associated Fuse Rating
10 A gG for control circuit conforming to IEC 60947-5-1 || 125 A at 690 V coordination type 1 for power circuit || 125 A at 690 V coordination type 2 for power circuit
Inrush Power In Va
140-140 VA cos phi 0.75 (at 20 °C)
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947
Pole Contact Composition
4 NO
Connections - Terminals
control circuit: screw clamp terminal 1 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminal 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminal 2 1-4 mm² - cable stiffness: solid without cable end || power circuit: screw clamp terminal 1 1-35 mm² - cable stiffness: solid without cable end || power circuit: screw clamp terminal 2 1-35 mm² - cable stiffness: solid without cable end
Coil Technology
without built-in bidirectional peak limiting diode suppressor
Operating Time
12...26 ms closing || 4...19 ms opening
Minimum Switching Voltage
17 V for control circuit
Maximum Operating Rate
3600 cyc/h 60 °C
Tightening Torque
control circuit 1.7 N.m screw clamp terminal flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminal Philips No 2 || power circuit 5 N.m screw clamp terminal flat Ø 6 mm hexagonal || power circuit 5 N.m screw clamp terminal Philips No 2 hexagonal || control circuit 1.7 N.m screw clamp terminal pozidriv No 2 || power circuit 5 N.m screw clamp terminal pozidriv No 2
Mechanical Durability
6000000 cycles
Auxiliary Contacts Type
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Compatibility Code
LC1D
Hold-In Power Consumption In Va
13-13 VA 60 Hz cos phi 0.3 (at 20 °C) || 15-15 VA 50 Hz cos phi 0.3 (at 20 °C)
Overvoltage Category
III
[Ui] Rated Insulation Voltage
control circuit 600 V CSA || control circuit 600 V UL || power circuit 600 V CSA || power circuit 600 V UL || control circuit 690 V IEC 60947-4-1 || power circuit 690 V IEC 60947-4-1
Heat Dissipation
4-5 W at 50/60 Hz for control circuit
Protective Cover
with

Specifications

[Uc] Control Circuit Voltage
120 V AC 50/60 Hz
[Ue] Rated Operational Voltage
power circuit 690 V AC 25...400 Hz
Range Of Product
TeSys Deca
Contactor Application
resistive load
Product Or Component Type
contactor
Utilisation Category
AC-1 || AC-3 || AC-3e || AC-4
[Ie] Rated Operational Current
80 A (at <60 °C) at 440 V AC AC-1 for power circuit
Poles Description
4P
Device Short Name
LC1D

Documents

Data Sheet

Download

Related products