contactor, TeSys F, 3P(3NO), AC-1, <=690V 1260 A, coil 220V AC
LC1F1250M7
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
Send request for price

Additional Information

Part Number
LC1F1250M7
UNSPSC
39121529
Tariff Code
8536490065
Country of Origin
CZ

Environment

Ambient Air Temperature For Operation
-5-40 °C
Height
338 mm
Net Weight
19 kg
Ambient Air Temperature For Storage
-60-80 °C
Protective Treatment
TH
Operating Altitude
9842.52 ft (3000 m) without derating
Width
309 mm
Depth
255 mm
Permissible Ambient Air Temperature Around The Device
-40-60 °C

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1505009EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI1505009EN
Eu Rohs Directive
Compliant with Exemptions

Complementary

Product Certifications
CB || UL || CSA || CQC || CE || UKCA || CCC
Power Dissipation Per Pole
120 W AC-1
Average Impedance
0.12 mOhm - Ith 1260 A 50 Hz
[Ith] Conventional Free Air Thermal Current
1260 A (at 40 °C)
Control Circuit Voltage Limits
operational 0.85...1.1 Uc 40...400 Hz 55 °C) || drop-out 0.25...0.5 Uc 40...400 Hz 55 °C)
Standards
EN 60947-4-1 || IEC 60947-4-1 || IEC 60947-1 || EN 60947-1 || JIS C8201-4-1
Mounting Support
plate
Control Circuit Type
AC 40...400 Hz
Rated Breaking Capacity
1890 A conforming to IEC 60947-4-1
Associated Fuse Rating
1000 A gG at <= 440 V
[Uimp] Rated Impulse Withstand Voltage
8 kV
Inrush Power In Va
1650-1650 VA, 40...400 Hz 0.9 20 °C)
Connections - Terminals
control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit bar 2 100 x 5 mm || power circuit bolted connection
Pole Contact Composition
3 NO
Operating Time
40...80 ms closing || 100...200 ms opening
Maximum Operating Rate
1200 cyc/h 55 °C
Tightening Torque
control circuit 1.2 N.m || power circuit 58 N.m
Compatibility Code
LC1F
Hold-In Power Consumption In Va
22-22 VA, 40...400 Hz 0.9 20 °C)
Overvoltage Category
III
[Ui] Rated Insulation Voltage
1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C
[Icw] Rated Short-Time Withstand Current
3000 A 40 °C - 3 min || 8000 A 40 °C - 10 s || 5200 A 40 °C - 30 s || 4000 A 40 °C - 1 min || 2000 A 40 °C - 10 min
Heat Dissipation
20-20 W

Specifications

[Uc] Control Circuit Voltage
220 V AC 40...400 Hz
Range Of Product
TeSys F
[Ue] Rated Operational Voltage
<= 460 V DC || <= 690 V AC 50/60 Hz
Contactor Application
resistive load
Product Or Component Type
contactor
Range
TeSys
Utilisation Category
AC-1
[Ie] Rated Operational Current
1260 A (at <40 °C) AC-1
Poles Description
3P
Device Short Name
LC1F

Documents

Data Sheet

Download

Related products