contactor, TeSys F, 3P(3NO), AC-1, <=1000V 1700A, coil 230V AC
LC1F1700P7
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
€3,530.03

Additional Information

Part Number
LC1F1700P7
UNSPSC
39121529
Tariff Code
8536490065
Country of Origin
CZ

Environment

Ambient Air Temperature For Operation
-5-40 °C
Height
332 mm
Net Weight
30 kg
Ambient Air Temperature For Storage
-60-80 °C
Protective Treatment
TH
Operating Altitude
9842.52 ft (3000 m) without derating
Width
438 mm
Depth
238.6 mm
Permissible Ambient Air Temperature Around The Device
-40-60 °C

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP110206EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI1102006EN
Eu Rohs Directive
Compliant with Exemptions

Complementary

Product Certifications
UL || CSA || CCC || CB Scheme || EAC || UKCA
Power Dissipation Per Pole
200 W AC-1
Average Impedance
0.1 mOhm - Ith 1700 A 50 Hz
[Ith] Conventional Free Air Thermal Current
1700 A (at 40 °C)
Control Circuit Voltage Limits
operational 0.85...1.1 Uc 40...400 Hz 55 °C) || drop-out 0.3...0.5 Uc 40...400 Hz 55 °C)
Standards
JIS C8201-4-1 || IEC 60947-4-1 || EN 60947-1 || EN 60947-4-1 || IEC 60947-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
Mounting Support
plate
Control Circuit Type
AC 40...400 Hz
Rated Breaking Capacity
2550 A conforming to IEC 60947-4-1
Associated Fuse Rating
1600 A gG at <= 440 V
[Uimp] Rated Impulse Withstand Voltage
8 kV
Inrush Power In Va
2200-2200 VA, 40...400 Hz 0.9 20 °C)
Connections - Terminals
control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit bar 3 100 x 5 mm || power circuit bolted connection
Pole Contact Composition
3 NO
Operating Time
100...170 ms opening || 40...75 ms closing
Maximum Operating Rate
600 cyc/h 55 °C
Tightening Torque
control circuit 1.2 N.m || power circuit 58 N.m
Compatibility Code
LC1F
Hold-In Power Consumption In Va
36-36 VA, 40...400 Hz 0.9 20 °C)
Overvoltage Category
III
[Ui] Rated Insulation Voltage
1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C || 1000 V UL 60947-4-1
[Icw] Rated Short-Time Withstand Current
10000 A 40 °C - 10 s || 7500 A 40 °C - 30 s || 5500 A 40 °C - 1 min || 4200 A 40 °C - 3 min || 3000 A 40 °C - 10 min
Heat Dissipation
36-36 W

Specifications

[Uc] Control Circuit Voltage
230 V AC 40...400 Hz
Range Of Product
TeSys F
[Ue] Rated Operational Voltage
<= 1000 V AC 50/60 Hz || <= 460 V DC
Contactor Application
resistive load
Product Or Component Type
contactor
Range
TeSys
Utilisation Category
AC-1
[Ie] Rated Operational Current
1700 A (at <40 °C) AC AC-1
Poles Description
3P
Device Short Name
LC1F

Documents

Data Sheet

Download

Related products