contactor, TeSys F, 3P(3NO), AC1, <=1000V AC 2600 A, coil 220V DC
LC1F2600MD
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Offer with manufacturer lead time
Ships in:On Request
Best price:
Send request for price

Additional Information

Part Number
LC1F2600MD
UNSPSC
39121529
Tariff Code
8536490065
Country of Origin
CZ

Specifications

[Uc] Control Circuit Voltage
220 V DC
Range Of Product
TeSys F
[Ue] Rated Operational Voltage
<= 1000 V AC 50/60 Hz
Contactor Application
resistive load
Product Or Component Type
contactor
Range
TeSys
Utilisation Category
AC-1
[Ie] Rated Operational Current
2600 A (at <60 °C) AC AC-1
Poles Description
3P
Device Short Name
LC1F

Environment

Ambient Air Temperature For Operation
-5-40 °C
Height
382 mm
Net Weight
36 kg
Ambient Air Temperature For Storage
-60-80 °C
Protective Treatment
TH
Ip Degree Of Protection
IP20 front face with shrouds IEC 60529 || IP20 front face with shrouds VDE 0106
Operating Altitude
9842.52 ft (3000 m) without derating
Width
519 mm
Depth
251 mm
Permissible Ambient Air Temperature Around The Device
-40-60 °C

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP110206EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI1102006EN
Eu Rohs Directive
Compliant with Exemptions

Complementary

Product Certifications
CB Scheme || CCC || CSA || UL || UKCA || EAC
Power Dissipation Per Pole
250 W AC-1
Average Impedance
0.1 mOhm - Ith 2600 A 50 Hz
[Ith] Conventional Free Air Thermal Current
2600 A (at 60 °C)
Control Circuit Voltage Limits
operational 0.85...1.1 Uc 55 °C) || drop-out 0.2...0.35 Uc 55 °C)
Standards
EN 60947-4-1 || IEC 60947-1 || IEC 60947-4-1 || EN 60947-1 || JIS C8201-4-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
Mounting Support
plate
Control Circuit Type
DC standard
Hold-In Power Consumption In W
18-18 W 20 °C
Rated Breaking Capacity
3900 A conforming to IEC 60947-4-1
Associated Fuse Rating
2500 A gG at <= 440 V
[Uimp] Rated Impulse Withstand Voltage
8 kV
Connections - Terminals
control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit bar 3 100 x 10 mm
Pole Contact Composition
3 NO
Operating Time
60...70 ms closing || 40...50 ms opening
Maximum Operating Rate
600 cyc/h 55 °C
Tightening Torque
control circuit 1.2 N.m || power circuit 58 N.m
Inrush Power In W
2600-2600 W 20 °C)
Compatibility Code
LC1F
Overvoltage Category
III
[Ui] Rated Insulation Voltage
1000 V IEC 60947-4-1 || 1000 V UL 60947-4-1
[Icw] Rated Short-Time Withstand Current
12000 A 40 °C - 10 s || 9000 A 40 °C - 30 s || 7000 A 40 °C - 1 min || 6000 A 40 °C - 3 min || 4000 A 40 °C - 10 min
Heat Dissipation
40-40 W

Documents

Data Sheet