Contactor body, TeSys F,3P(3NO), AC-3, <=440V 630 A without coil
LC1F630
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
$3,150.62
1
Payment methods:
A total of 8 Parts In-Stock from 20 Distributors

Additional Information

Part Number
LC1F630
UNSPSC
39121529
Tariff Code
8536490065
Country of Origin
CZ

Environment

Mechanical Robustness
vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open6 Gn for 1/2 sine wave (11 ms) || shocks contactor closed15 Gn for 1/2 sine wave (11 ms)
Ambient Air Temperature For Operation
-5-55 °C
Height
304 mm
Net Weight
18.6 kg
Ambient Air Temperature For Storage
-60-80 °C
Protective Treatment
TH
Ip Degree Of Protection
IP20 front face with shrouds IEC 60529 || IP20 front face with shrouds VDE 0106
Operating Altitude
9842.52 ft (3000 m) without derating
Width
309 mm
Depth
255 mm
Permissible Ambient Air Temperature Around The Device
-40-70 °C

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1505009EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI1505009EN
Eu Rohs Directive
Compliant with Exemptions

Complementary

Product Certifications
ABS || UL || RINA || DNV || CSA || CB || LROS (Lloyds register of shipping) || BV || RMRoS || UKCA
Power Dissipation Per Pole
120 W AC-1 || 48 W AC-3
Average Impedance
0.12 mOhm - Ith 1000 A 50 Hz
Control Circuit Voltage Limits
operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil || drop-out: 0.25...0.5 Uc AC 40...400 Hz with LX1/LX9 coil || operational: 0.85...1.1 Uc DC with LX4 coil || drop-out: 0.2...0.35 Uc DC with LX4 coil
[Ith] Conventional Free Air Thermal Current
1000 A (at 40 °C) || 1250 A
Standards
EN 60947-4-1 || IEC 60947-4-1 || IEC 60947-1 || JIS C8201-4-1 || EN 60947-1
[Uc] Control Circuit Voltage
48...1000 V AC 40...400 Hz with LX1/LX9 coil || 48...440 V DC with LX4 coil
Mounting Support
plate
Rated Breaking Capacity
5040 A conforming to IEC 60947-4-1
Irms Rated Making Capacity
6300 A AC conforming to IEC 60947-4-1
Associated Fuse Rating
630 A aM at <= 440 V || 1000 A gG at <= 440 V
[Uimp] Rated Impulse Withstand Voltage
8 kV
Connections - Terminals
power circuit bar 2 60 x 5 mm || power circuit bolted connection || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²solid without cable end || control circuit screw clamp terminals 1 1-4 mm² || control circuit screw clamp terminals 2 1-4 mm²
Inrush Power In Va
1500-1730 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil || 1420-1920 VA (at 20 °C)with LX4 coil
Maximum Operating Rate
1200 cyc/h 55 °C
Operating Time
40...80 ms closing with LX1/LX9 coil || 100...200 ms opening with LX1/LX9 coil || 60...70 ms closing with LX4 coil || 40...50 ms opening with LX4 coil
Tightening Torque
power circuit 58 N.m || control circuit 1.2 N.m
Mechanical Durability
5 Mcycles
Compatibility Code
LC1F
Hold-In Power Consumption In Va
20-25 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil || 6.5-12.5 VA (at 20 °C)with LX4 coil
Overvoltage Category
III
[Ui] Rated Insulation Voltage
1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C
[Icw] Rated Short-Time Withstand Current
5050 A 40 °C - 10 s || 4400 A 40 °C - 30 s || 3400 A 40 °C - 1 min || 2200 A 40 °C - 3 min || 1600 A 40 °C - 10 min
Heat Dissipation
20-20 W

Specifications

[Ue] Rated Operational Voltage
<= 1000 V AC 50/60 Hz || <= 460 V DC
Contactor Application
resistive load || motor control
Product Or Component Type
contactor
Product Name
TeSys F
Range
TeSys
Pole Contact Composition
3 NO
[Ie] Rated Operational Current
1000 A 40 °C) <= 440 V AC AC-1 || 630 A 55 °C) <= 440 V AC AC-3
Utilisation Category
AC-4 || AC-1 || AC-3
Poles Description
3P
Motor Power Kw
335 kW at 380...400 V AC 50/60 Hz (AC-3) || 375 kW at 415 V AC 50/60 Hz (AC-3) || 400 kW at 440 V AC 50/60 Hz (AC-3) || 400 kW at 500 V AC 50/60 Hz (AC-3) || 450 kW at 1000 V AC 50/60 Hz (AC-3) || 200 kW at 220...240 V AC 50/60 Hz (AC-3) || 450 kW at 660...690 V AC 50/60 Hz (AC-3) || 100 kW at 400 V AC 50/60 Hz (AC-4)
Device Short Name
LC1F

Documents

Data Sheet

Download

CAD Models

Trace parts
Trace parts
Download

Related products