contactor, TeSys F, 4P(4NO), AC-1, <=440V 1600A, coil 110V AC
LC1F7804F7
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
65 491,52 zł

Additional Information

Part Number
LC1F7804F7
UNSPSC
39121529
Tariff Code
8536490065
Country of Origin
CZ

Environment

Ambient Air Temperature For Operation
-5-55 °C
Height
434 mm
Net Weight
48 kg
Ambient Air Temperature For Storage
-60-80 °C
Protective Treatment
TH
Ip Degree Of Protection
IP20 front face with shrouds IEC 60529 || IP20 front face with shrouds VDE 0106
Operating Altitude
9842.52 ft (3000 m) without derating
Width
862 mm
Depth
255 mm
Permissible Ambient Air Temperature Around The Device
-40-70 °C

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1505009EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI1505009EN
Eu Rohs Directive
Compliant with Exemptions

Complementary

Product Certifications
CCC || CB || UL || DNV || BV || LROS (Lloyds register of shipping) || ABS || RINA || RMRoS || UKCA
Power Dissipation Per Pole
250 W AC-1
Average Impedance
0.1 mOhm - Ith 1600 A 50 Hz
[Ith] Conventional Free Air Thermal Current
1600 A (at 40 °C)
Control Circuit Voltage Limits
operational 0.85...1.1 Uc 40...400 Hz 55 °C) || drop-out 0.2...0.4 Uc 40...400 Hz 55 °C)
Standards
IEC 60947-1 || EN 60947-4-1 || IEC 60947-4-1 || EN 60947-1 || JIS C8201-4-1
Mounting Support
plate
Control Circuit Type
AC 40...400 Hz
Rated Breaking Capacity
6240 A conforming to IEC 60947-4-1
Associated Fuse Rating
1600 A gG at <= 440 V || 800 A aM at <= 440 V
[Uimp] Rated Impulse Withstand Voltage
8 kV
Inrush Power In Va
2100-2100 VA, 40...400 Hz 0.9 20 °C)
Connections - Terminals
control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit bar 2 100 x 5 mm || power circuit bolted connection
Pole Contact Composition
4 NO
Operating Time
40...80 ms closing || 130...230 ms opening
Maximum Operating Rate
600 cyc/h 55 °C
Mechanical Durability
5 Mcycles
Tightening Torque
control circuit 1.2 N.m || power circuit 58 N.m
Compatibility Code
LC1F
Hold-In Power Consumption In Va
50-50 VA, 40...400 Hz 0.9 20 °C)
Overvoltage Category
III
[Ui] Rated Insulation Voltage
1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C
[Icw] Rated Short-Time Withstand Current
3000 A 40 °C - 3 min || 6250 A 40 °C - 10 s || 5600 A 40 °C - 30 s || 4600 A 40 °C - 1 min || 2200 A 40 °C - 10 min
Heat Dissipation
44-44 W

Specifications

[Uc] Control Circuit Voltage
110 V AC 40...400 Hz
Range Of Product
TeSys F
[Ue] Rated Operational Voltage
<= 1000 V AC 50/60 Hz || <= 460 V DC
Contactor Application
resistive load
Product Or Component Type
contactor
Range
TeSys
Utilisation Category
AC-1
[Ie] Rated Operational Current
1600 A (at <40 °C) at <= 440 V AC AC-1
Poles Description
4P
Device Short Name
LC1F

Documents

Data Sheet

Download

CAD Models

Trace parts
Trace parts
Download

Related products