Contactor, high power, TeSys Giga, advanced version, AC-3, <= 440V, 630A, 3 pole/NO, 48-130VAC/DC coil
LC1G630EHEA
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
€1,361.14

Additional Information

Part Number
LC1G630EHEA
UNSPSC
39121529
Tariff Code
8536490065

Specifications

[Uc] Control Circuit Voltage
48...130 V AC 50/60 Hz || 48...130 V DC
[Ue] Rated Operational Voltage
<= 1000 V AC 50/60 Hz || <= 460 V DC
Range Of Product
TeSys Giga
Control Circuit Voltage Limits
operational: 0.8 Uc Min...1.1 Uc Max (at <60 °C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C)
Contactor Application
power switching || motor control
Product Or Component Type
contactor
Range
TeSys
Utilisation Category
AC-1 || AC-3 || AC-3e || AC-4 || AC-5a || AC-5b || AC-6a || AC-6b || AC-8b || AC-8a || DC-1 || DC-3 || DC-5
[Ie] Rated Operational Current
1050 A (at <40 °C) at <= 1000 V AC-1 || 630 A (at <60 °C) at <= 440 V AC-3
Poles Description
3P
Device Short Name
LC1G

Environment

Ambient Air Temperature For Operation
-25-60 °C
Ambient Air Temperature For Storage
-60-80 °C
Protective Treatment
TH
Ip Degree Of Protection
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Mechanical Robustness
vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
Color
dark grey
Permissible Ambient Air Temperature Around The Device
-40-70 °C at Uc

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP2105013
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation
X
Circularity Profile
ENVEOLI2105013
Eu Rohs Directive
Compliant with Exemptions
Halogen Content Performance
Halogen free plastic parts product

Complementary

Product Certifications
CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
Height
388.5 mm
Power Dissipation Per Pole
70 W AC-1 - Ith 1050 A || 26 W AC-3 - Ith 630 A
Average Impedance
0.000065 Ohm
Auxiliary Contact Composition
1 NO + 1 NC
Connection Pitch
70 mm
[Ith] Conventional Free Air Thermal Current
1050 A (at 40 °C)
Standards
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1
Mounting Support
plate
Hold-In Power Consumption In W
8.8-8.8 W
Rated Breaking Capacity
5550 A at 440 V
Irms Rated Making Capacity
7220 A at 440 V
Associated Fuse Rating
630 A aM at <= 440 V for motor || 500 A aM at <= 690 V for motor || 1250 A gG at <= 690 V
Net Weight
17.3 kg
[Uimp] Rated Impulse Withstand Voltage
8 kV
Inrush Power In Va
560-560 VA
Pole Contact Composition
3 NO
Connections - Terminals
power circuit: bar 2 - busbar cross section: 52 x 20 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control circuit: push-in 1 0.25-2.5 mm² - cable stiffness: flexible with cable end || control circuit: push-in 2 0.5-1.0 mm² with cable end || control circuit: push-in 0.75-2.5 mm² - cable stiffness: solid stranded without cable end || control circuit: push-in 0.75-2.5 mm² - cable stiffness: flexible with cable end
Coil Technology
built-in bidirectional peak limiting
Operating Time
40...70 ms closing || 15...50 ms opening
Maximum Operating Rate
600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1 || 150 cyc/h AC-4
Mechanical Durability
5 Mcycles
Tightening Torque
58 N.m
Compatibility Code
LC1G
Hold-In Power Consumption In Va
12-12 VA
Width
211 mm
Overvoltage Category
III
Depth
266 mm
Maximum Horse Power Rating
250 hp at 200/208 V 60 Hz || 300 hp at 230/240 V 60 Hz || 600 hp at 460/480 V 60 Hz || 700 hp at 575/600 V 60 Hz
Motor Power Kw
180 kW at 230 V AC 50/60 Hz (AC-3e) || 315 kW at 400 V AC 50/60 Hz (AC-3e) || 335 kW at 415 V AC 50/60 Hz (AC-3e) || 355 kW at 440 V AC 50/60 Hz (AC-3e) || 375 kW at 500 V AC 50/60 Hz (AC-3e) || 500 kW at 690 V AC 50/60 Hz (AC-3e) || 450 kW at 1000 V AC 50/60 Hz (AC-3e) || 200 kW at 230 V AC 50/60 Hz (AC-3) || 335 kW at 400 V AC 50/60 Hz (AC-3) || 375 kW at 415 V AC 50/60 Hz (AC-3) || 400 kW at 440 V AC 50/60 Hz (AC-3) || 400 kW at 500 V AC 50/60 Hz (AC-3) || 500 kW at 690 V AC 50/60 Hz (AC-3) || 450 kW at 1000 V AC 50/60 Hz (AC-3) || 180 kW at 230 V AC 50/60 Hz (AC-4) || 315 kW at 400 V AC 50/60 Hz (AC-4) || 335 kW at 415 V AC 50/60 Hz (AC-4) || 355 kW at 440 V AC 50/60 Hz (AC-4) || 375 kW at 500 V AC 50/60 Hz (AC-4) || 450 kW at 690 V AC 50/60 Hz (AC-4) || 355 kW at 1000 V AC 50/60 Hz (AC-4)
[Ui] Rated Insulation Voltage
1000 V
Inrush Power In W
440 W
[Icw] Rated Short-Time Withstand Current
5.05 kA - 10 s || 4.4 kA - 30 s || 3.4 kA - 1 min || 2.2 kA - 3 min || 1.6 kA - 10 min