TeSys Deca , star delta starter , 3 x 3P (3 NO) , 32 A , 230 V AC coil
LC3D32AP7
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
A total of 10 Parts In-Stock from 16 Distributors

Environment

Mechanical Robustness
vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
Ambient Air Temperature For Operation
-40-70 °C at Uc
Climatic Withstand
IACS E10 || IEC 60947-1 Annex Q category D
Pollution Degree
3
Insulation Resistance
> 10 MOhm for signalling circuit
Flame Retardance
V1 conforming to UL 94
Ambient Air Temperature For Storage
-60-80 °C
Protective Treatment
TH IEC 60068-2-30
Ip Degree Of Protection
IP20 front face IEC 60529
Operating Altitude
9842.52 ft (3000 m) without derating
Fire Resistance
850 °C IEC 60695-2-1

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP110229EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
ENVEOLI110229EN
Eu Rohs Directive
Compliant

Complementary

Non-Overlap Time
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Minimum Switching Current
5 mA for signalling circuit
Height
124 mm
Control Circuit Voltage Limits
drop-out: 0.3...0.6 Uc at 50/60 Hz (at <60 °C) || operational: 0.8...1.1 Uc at 50 Hz (at <60 °C) || operational: 0.85...1.1 Uc at 60 Hz (at <60 °C)
Starting Time
30 s
Net Weight
2.03 kg
Inrush Power In Va
70-70 VA 60 Hz cos phi 0.75 (at 20 °C) || 70-70 VA 50 Hz cos phi 0.75 (at 20 °C)
Connections - Terminals
control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end || power circuit: screw clamp terminals 1 2.5-10 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 2 2.5-10 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 1 1-10 mm² - cable stiffness: flexible with cable end || power circuit: screw clamp terminals 2 1.5-6 mm² - cable stiffness: flexible with cable end || power circuit: screw clamp terminals 1 1.5-10 mm² - cable stiffness: solid without cable end || power circuit: screw clamp terminals 2 2.5-10 mm² - cable stiffness: solid without cable end
Coil Technology
without built-in suppressor module
Maximum Operating Rate
30 cyc/h 60 °C
Signalling Circuit Frequency
25...400 Hz
Tightening Torque
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2 || power circuit 1.7 N.m screw clamp terminals pozidriv No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2
Mechanical Durability
15 Mcycles
Auxiliary Contacts Type
mechanically linked IEC 60947-5-1 3 x 1 NO + 1 NC || mirror contact IEC 60947-4-1 3 x 1 NC
Hold-In Power Consumption In Va
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20 °C) || 7-7 VA 50 Hz cos phi 0.3 (at 20 °C)
Switching Voltage
17 V signalling circuit
Width
166 mm
Depth
149 mm
Heat Dissipation
2-3 W 50/60 Hz

Specifications

Product Certifications
GOST || RINA || UL || CSA || BV || DNV || LROS (Lloyds register of shipping) || CCC || GL
Interlocking Type
mechanical
[Uc] Control Circuit Voltage
230 V AC 50/60 Hz
[Ue] Rated Operational Voltage
power circuit <= 690 V AC 25...400 Hz
Standards
EN 60947-4-1 || IEC 60947-5-1 || CSA C22.2 No 14 || EN 60947-5-1 || UL 508 || IEC 60947-4-1 || IEC 60335-1
Pole Contact Composition
3 x 3 NO
Mounting Support
plate
Control Circuit Type
AC 50/60 Hz
Contactor Application
motor control
Product Or Component Type
star delta starter
Product Name
TeSys Deca
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947
Range
TeSys || TeSys Deca
Device Presentation
pre-wired
Utilisation Category
AC-3
[Ie] Rated Operational Current
32 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
Auxiliary Contact Composition
1 NC KM1 star contactor
Electrical Durability
1.65 Mcycles 32 A AC-3 <= 440 V
Provided Equipment
protective cover
Overvoltage Category
III
Motor Power Kw
15 kW 220/230 V AC 50/60 Hz || 25 kW 380/400 V AC 50/60 Hz || 30 kW 415 V AC 50/60 Hz || 30 kW 440 V AC 50/60 Hz
[Ui] Rated Insulation Voltage
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
Device Short Name
LC3D
Poles Description
3 x 3P

Documents

Data Sheet

Download

Related products