Circuit breaker, PowerPacT L, 600A, 3 pole, 500VDC, 50kA, lugs, thermal magnetic, 80%
LLL37060D33
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Environment

Ambient Air Temperature For Operation
-2-70 °C
Standards
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Product Certifications
UL || CSA || NOM
Ip Degree Of Protection
front cover IP40
Pollution Degree
3 IEC 60947-1
Ambient Air Temperature For Storage
-50-85 °C
Operating Altitude
< 6561.68 ft (2000 m) without derating || 5000 m with derating

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1406010EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI1406010EN
Eu Rohs Directive
Compliant with Exemptions

Complementary

Mounting Mode
unit mount lug)
Terminal Identifier
AL600LS52K3
[Ics] Rated Service Breaking Capacity
125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Trip Unit Technology
thermal-magnetic
Height
340 mm
[Ue] Rated Operational Voltage
500 V DC
Tightening Torque
50-50 N.m 70-240 mm² (2 x AWG 2/0...500 kcmil) || 50-50 N.m 35-300 mm² (AWG 2...600 kcmil)
Mounting Support
lug
Breaking Capacity Code
L
Magnetic Tripping Current
1500-3000 A
Local Signalling
switched off (OFF) 1 trip indicator green)
Electrical Connection
lugs, line || lugs, load
Net Weight
6.2 kg
[Uimp] Rated Impulse Withstand Voltage
8 kV IEC 60947-2
Control Type
toggle
Circuit Breaker Application
HACR rated
Wire Stripping Length
31 mm || 61 mm
Utilisation Category
category A
Breaking Capacity
125 kA 240 V AC 50/60 Hz UL 489 || 100 kA 480 V AC 50/60 Hz UL 489 || 50 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 50 kA 500 V DC UL 489
[Ui] Rated Insulation Voltage
750 V IEC 60947-2
Suitability For Isolation
yes IEC 60947-2
Communication Interface
Modbus || Ethernet
Poles Description
3P
Awg Gauge
2 x AWG 2/0...500 kcmil aluminium/copper
Color
Black
Width
140 mm
Depth
110 mm

Specifications

Product Or Component Type
circuit breaker
Product Name
PowerPact L
Range
PowerPact
Device Application
distribution
Device Short Name
L-Frame

Documents

Data Sheet

Download