Schneider Electric
LP1D65008BD
IEC contactor, TeSys Deca, nonreversing, 80A resistive, 4 pole, 2 NO and 2 NC, 24VDC coil, open style
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
$1,001.36
1
Payment methods:
A total of 10 Parts In-Stock from 18 Distributors
Product Conditions:
Offer with manufacturer lead time
Ships in:On Request
Best price:
€177.61
Additional Information
- Part Number
- LP1D65008BD
- UNSPSC
- 39121529
- Tariff Code
- 8536490075
- Country of Origin
- CZ
Environment
- Product Certifications
- UL || CSA || CCC || EAC || UKCA || CB || DNV-GL || RINA || BV || LROS (Lloyds register of shipping)
- Height
- 127 mm
- Standards
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
- Net Weight
- 2.22 kg
- Flame Retardance
- V1 conforming to UL 94
- Ip Degree Of Protection
- IP20 front face IEC 60529
- Mechanical Robustness
- shocks contactor open 8 Gn for 11 ms) || shocks contactor closed 10 Gn for 11 ms) || vibrations contactor opened 2 Gn, 5...300 Hz) || vibrations contactor closed 3 Gn, 5...300 Hz)
- Operating Altitude
- 0...9842.52 ft (0...3000 m)
- Fire Resistance
- 850 °C IEC 60695-2-1
- Width
- 85 mm
- Depth
- 182 mm
- Permissible Ambient Air Temperature Around The Device
- -40-60 °C || 60-70 °C with derating
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP110205EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Toxic Heavy Metal Free
- Yes
- Reach Regulation
- Free of Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
- Reach Free Of Svhc
- Yes
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Circularity Profile
- N/A
- Eu Rohs Directive
- Compliant
Complementary
- Power Dissipation Per Pole
- 9.6 W AC-1
- Average Impedance
- 1.5 mOhm - Ith 80 A 50 Hz for power circuit
- [Ith] Conventional Free Air Thermal Current
- 80 A (at 60 °C) for power circuit
- Control Circuit Voltage Limits
- 0.1...0.3 Uc -40-55 °C drop-out DC || 0.85...1.1 Uc -40-55 °C operational DC
- Mounting Support
- plate || rail
- Contact Compatibility
- M3
- Control Circuit Type
- DC DC standard
- Safety Reliability Level
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Pollution Degree
- 3
- Hold-In Power Consumption In W
- 22-22 W 20 °C
- Rated Breaking Capacity
- 1000 A at 440 V for power circuit conforming to IEC 60947
- Irms Rated Making Capacity
- 1000 A at 440 V for power circuit conforming to IEC 60947
- Associated Fuse Rating
- 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV IEC 60947
- Pole Contact Composition
- 2 NO + 2 NC
- Connections - Terminals
- power circuit: screw clamp terminals 1 2.5-25 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 2 2.5-16 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 1 2.5-25 mm² - cable stiffness: flexible with cable end || power circuit: screw clamp terminals 2 2.5-10 mm² - cable stiffness: flexible with cable end || power circuit: screw clamp terminals 1 2.5-25 mm² - cable stiffness: solid || power circuit: screw clamp terminals 2 2.5-16 mm² - cable stiffness: solid || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid
- Coil Technology
- built-in bidirectional peak limiting diode suppressor
- Time Constant
- 75 ms
- Operating Time
- 4...19 ms opening || 12...26 ms closing
- Maximum Operating Rate
- 3600 cyc/h 60 °C
- Tightening Torque
- power circuit 8 N.m screw clamp terminals 25-35 mm² hexagonal 4 mm || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 5 N.m screw clamp terminals 1-25 mm² hexagonal 4 mm || control circuit 1.7 N.m screw clamp terminals pozidriv No 2
- Electrical Durability
- 1.5 Mcycles 80 A AC-1 <= 440 V
- Mechanical Durability
- 10 Mcycles
- Inrush Power In W
- 22-22 W 20 °C)
- Compatibility Code
- LP1D
- Overvoltage Category
- III
- [Ui] Rated Insulation Voltage
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL
- [Icw] Rated Short-Time Withstand Current
- 110 A 40 °C - 10 min for power circuit || 260 A 40 °C - 1 min for power circuit || 520 A 40 °C - 10 s for power circuit || 900 A 40 °C - 1 s for power circuit
- Protective Cover
- without
Specifications
- [Uc] Control Circuit Voltage
- 24 V DC
- [Ue] Rated Operational Voltage
- power circuit <= 1000 V AC 25...400 Hz
- Range Of Product
- TeSys Deca
- Contactor Application
- resistive load
- Product Or Component Type
- contactor
- Range
- TeSys
- Utilisation Category
- AC-1
- [Ie] Rated Operational Current
- 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
- Poles Description
- 4P
- Device Short Name
- LP1D
Documents
Data Sheet
DownloadCAD Models
traceparts
DownloadOther Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther