Schneider Electric
LR9D08KITD09BD
Tesys motor starter kit, LC1D09BD contactor, LR9D08 thermal overload relay
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Specifications
- Product Certifications
- LROS (Lloyds register of shipping) || CSA || UL || GOST || DNV || CCC || GL || BV || RINA
- [Uc] Control Circuit Voltage
- 24 V DC
- [Ue] Rated Operational Voltage
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Power Dissipation Per Pole
- 1.56 W AC-1 || 0.2 W AC-3
- Average Impedance
- 2.5 mOhm - Ith 25 A 50 Hz for power circuit
- Auxiliary Contact Composition
- 1 NO + 1 NC
- [Ith] Conventional Free Air Thermal Current
- 25 A (at 60 °C) for power circuit || 10 A (at 60 °C) for signalling circuit
- Phase Failure Sensitivity
- phase difference > 40% 3-3 s IEC 60947-4-1
- Mounting Support
- plate || rail
- Control Circuit Type
- DC standard
- Standards
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
- Safety Reliability Level
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Contactor Application
- motor control || resistive load
- Relay Application
- motor protection
- Rated Breaking Capacity
- 250 A at 440 V for power circuit conforming to IEC 60947
- Product Or Component Type
- motor starter
- Irms Rated Making Capacity
- 250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1
- Associated Fuse Rating
- 10 A gG for signalling circuit conforming to IEC 60947-5-1 || 25 A gG at <= 690 V coordination type 1 for power circuit || 20 A gG at <= 690 V coordination type 2 for power circuit
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV IEC 60947
- Connections - Terminals
- power circuit screw clamp terminals 1 1-4 mm²flexible without cable end || power circuit screw clamp terminals 2 1-4 mm²flexible without cable end || power circuit screw clamp terminals 1 1-4 mm²flexible with cable end || power circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || power circuit screw clamp terminals 1 1-4 mm²solid without cable end || power circuit screw clamp terminals 2 1-4 mm²solid without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end
- Range
- TeSys
- Pole Contact Composition
- 3 NO
- Utilisation Category
- AC-4 || AC-1 || AC-3
- Maximum Operating Rate
- 3600 cyc/h 60 °C
- Tightening Torque
- power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2
- Mechanical Durability
- 30 Mcycles
- Poles Description
- 3P
- Operating Time
- 53.55...72.45 ms closing || 16...24 ms opening
- Overvoltage Category
- III
- Motor Power Kw
- 2.2 kW at 220...230 V AC 50/60 Hz (AC-3) || 4 kW at 380...400 V AC 50/60 Hz (AC-3) || 4 kW at 415...440 V AC 50/60 Hz (AC-3) || 5.5 kW at 500 V AC 50/60 Hz (AC-3) || 5.5 kW at 660...690 V AC 50/60 Hz (AC-3) || 2.2 kW at 400 V AC 50/60 Hz (AC-4)
- Maximum Horse Power Rating
- 1 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 2 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 2 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 5 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 7.5 hp at 575/600 V AC 50/60 Hz for 3 phase motors || 0.33 hp at 115 V AC 50/60 Hz for 1 phase motors
- [Ui] Rated Insulation Voltage
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
- Protective Cover
- with
Environment
- Mechanical Robustness
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
- Ambient Air Temperature For Operation
- -5-60 °C
- Height
- 77 mm
- Standards
- UL 60947-4-1 || IEC 60947-4-1 || GB 14048.4 || CSA C22.2
- Ambient Air Temperature For Operation
- -25-70 °C IEC 60255-8
- Pollution Degree
- 3
- Product Certifications
- TÜV || CSA || cULus || CCC
- Electromagnetic Compatibility
- surge withstand 2 kV common mode IEC 61000-4-5 || resistance to electrostatic discharge 8 kV IEC 61000-4-2 || immunity to radiated radio-electrical interference 10 V/m IEC 61000-4-3 || immunity to fast transients 2 kV IEC 61000-4-4
- Dielectric Strength
- 6 kV 50 Hz IEC 60255-5
- Net Weight
- 0.48 kg
- Depth
- 79.9 mm
- Flame Retardance
- V1 conforming to UL 94
- Ambient Air Temperature For Storage
- -60-80 °C
- Width
- 45 mm
- Height
- 72.5 mm
- Protective Treatment
- TH IEC 60068-2-30
- Net Weight
- 0.18 kg
- Ip Degree Of Protection
- IP20 front face IEC 60529
- Operating Altitude
- 6561.68 ft (2000 m) without derating
- Operating Altitude
- 9842.52 ft (3000 m) without derating
- Fire Resistance
- 850 °C IEC 60695-2-1
- Depth
- 95 mm
- Permissible Ambient Air Temperature Around The Device
- -40-70 °C at Uc
Complementary
- Time Range
- 1.5...4 min - automatic reset time
- Non-Overlap Time
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Minimum Switching Current
- 5 mA for signalling circuit
- [Ith] Conventional Free Air Thermal Current
- 5 A signalling circuit
- Tightening Torque
- control circuit 0.8 N.m screw clamp terminals || power circuit 3.1 N.m screw clamp terminals
- Control Circuit Voltage Limits
- drop-out 0.1...0.25 Uc DC 60 °C) || operational 0.7...1.25 Uc DC 60 °C)
- [Ue] Rated Operational Voltage
- 690 V power circuit || 660 V signalling circuit
- Contact Compatibility
- M4
- Thermal Protection Adjustment Range
- 0.4-2 A
- Power Consumption In W
- 300 mW
- Contactor Coil Voltage
- 24 V DC standard
- Hold-In Power Consumption In W
- 5.4-5.4 W 20 °C
- Insulation Resistance
- > 10 MOhm for signalling circuit
- Ip Degree Of Protection
- front face IP20 IEC 60529 || front face IP20 VDE 0106
- Thermal Overload Class
- class 5…30
- Associated Fuse Rating
- 5 A gG signalling circuit || 5 A BS signalling circuit
- Power Range
- 1.1-2 kW 200-240 V 3 phase || 2.2-3 kW 380-440 V 3 phase || 4-6 kW 380-440 V 3 phase || 4-6 kW 480-500 V 3 phase
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV
- Connections - Terminals
- control circuit screw clamp terminals 1 2.5-2.5 mm² solid or flexible - without cable end || power circuit screw clamp terminals 1 16-16 mm² solid or flexible - without cable end
- Coil Technology
- built-in bidirectional peak limiting diode suppressor
- Time Constant
- 28 ms
- [Ui] Rated Insulation Voltage
- power circuit 1000 V || signalling circuit 690 V
- Motor Starter Type
- direct on-line contactor
- Minimum Switching Voltage
- 17 V for signalling circuit
- Tripping Threshold
- 1.25 In IEC 60947-4-1
- Signalling Circuit Frequency
- 25...400 Hz
- Control Type
- Red push-button stop and manual reset || White 2 microswitches adjustable trip class || Red knob automatic reset || White dial full-load current adjustment
- Mounting Support
- under contactor || plate, with specific accessories || rail, with specific accessories
- Inrush Power In W
- 5.4-5.4 W 20 °C)
- Auxiliary Contacts Type
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Mechanical Robustness
- vibrations 10...150 Hz 6 Gn) IEC 60068-2-6 || shocks 11 ms 15 gn) IEC 60068-2-7
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1502001EN
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI1502001EN
- Eu Rohs Directive
- Compliant with Exemptions
Documents
Data Sheet
DownloadOther Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther