electronic thermal overload relay, TeSys Deca, 90...150A, class 10...20
LR9D69
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
A total of 10 Parts In-Stock from 14 Distributors
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
€184.79

Additional Information

Part Number
LR9D69
UNSPSC
39122330
Tariff Code
8536490080
Country of Origin
FR

Environment

Product Certifications
UL || CSA || CCC
Mechanical Robustness
vibrations2 Gn, 5...300 Hz IEC 60068-2-6 || shocks13 Gn for 11 ms IEC 60068-2-7
Standards
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4 || GB/T 14048.5
Climatic Withstand
IACS E10
Ambient Air Temperature For Operation
-20-60 °C without derating IEC 60947-4-1
Dielectric Strength
1.89 kV 50 Hz IEC 60947-1
Ip Degree Of Protection
IP20 conforming to IEC 60529
Ambient Air Temperature For Storage
-60-70 °C
Operating Altitude
<= 6561.68 ft (2000 m) without derating

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP2212018
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI2212018
Eu Rohs Directive
Compliant with Exemptions

Complementary

Network Frequency
50-60 Hz
Height
118 mm
[Ith] Conventional Free Air Thermal Current
5 A signalling circuit
Auxiliary Contact Composition
1 NO + 1 NC
Connections - Terminals
power circuit bars || control circuit screw clamp terminals 1 0.5-1.5 mm² flexible without cable end || control circuit screw clamp terminals 2 0.5-1.5 mm² flexible without cable end || alarm circuit screw clamp terminals 1 0.5-1.5 mm² flexible without cable end
Phase Failure Sensitivity
tripping in 4 s +/- 20 % IEC 60947-4-1
[Ue] Rated Operational Voltage
690 V AC 0...400 Hz power circuit IEC 60947-4-1
Switching Capacity In Ma
0...150 mA
Associated Fuse Rating
4 A gG for signalling circuit || 4 A BS for signalling circuit
Net Weight
0.9 kg
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947-1
Maximum Voltage Drop
<2.5 V closed state
Supply Voltage Limits
17-32 V
Tripping Threshold
1.05 +/- 0.06 In alarm IEC 60947-4-1 || 1.12 +/- 0.06 In de-energisation IEC 60947-4-1
Tightening Torque
alarm circuit 0.45 N.m screw clamp terminals || power circuit 18 N.m bars M8 || control circuit 1.2 N.m screw clamp terminals
Control Type
Red push-button stop || Blue push-button reset
Mounting Support
under contactor || rail
Width
115 mm
Depth
125 mm
[Us] Rated Supply Voltage
24 V DC
Temperature Compensation
-20-60 °C

Specifications

Signalling Function
alarm
Network Type
AC
Thermal Protection Adjustment Range
90-150 A
Relay Application
motor protection
Product Or Component Type
electronic thermal overload relay
Product Name
TeSys LRD || TeSys Deca
Thermal Overload Class
class 10/20 IEC 60947-4-1
Range
TeSys
[Ui] Rated Insulation Voltage
power circuit 1000 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL
Product Compatibility
NSX circuit breaker || LC1D115 || LC1D150
Device Short Name
LR9D

Documents

Data Sheet

Download

CAD Models

Trace parts
Trace parts
Download

Related products