Schneider Electric
LTMCU
Operator control unit, TeSys T, for LTMR controller
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
$341.55
1
Payment methods:
A total of 18 Parts In-Stock from 20 Distributors
Product Conditions:
Environment
- Mechanical Robustness
- shocks15 Gn for 11 ms EN/IEC 60068-2-27 || vibrations4 Gn, 5...300 Hz EN/IEC 60068-2-6
- Ambient Air Temperature For Operation
- -20-60 °C
- Flame Retardance
- V2 conforming to UL 94
- Relative Humidity
- 15-95 %
- Ambient Air Temperature For Storage
- -40-80 °C
- Protective Treatment
- TC 12 humidity cycles 55 °C EN/IEC 60068-2-30
- Fire Resistance
- 650 °C EN/IEC 60947-1
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP060308EN_V2
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI100411EN_V2
- Eu Rohs Directive
- Compliant with Exemptions
- Halogen Content Performance
- Halogen free plastic parts product
Complementary
- Product Certifications
- C-tick || EAC || CSA || NOM || UL || CE
- Height
- 70 mm
- Standards
- UL 60947-4-1A || CSA C22.2 No 60947-4-1 || EN/IEC 61131-2
- Power Dissipation
- 1 W
- Supply
- via the controller
- Net Weight
- 0.4 kg
- Ip Degree Of Protection
- IP54 EN/IEC 60947-4-1 front) || IP20 EN/IEC 60947-4-1 rear)
- Electromagnetic Compatibility
- electrostatic discharge, level 3, 8 kV air, 4 kV contact, conforming to EN/IEC 61000-4-2 || radiated RF fields, level 3, 10 V/m, conforming to EN/IEC 61000-4-3 || conducted RF disturbances, level 3, 10 V, conforming to EN/IEC 61000-4-6 || surges (shielded access), level 3, 2 kV, conforming to EN/IEC 61000-4-5 || fast transient bursts (shielded access), level 3, 2 kV, conforming to EN/IEC 61000-4-4
- Mounting Mode
- flush-mounted
- Maximum Supply Current
- 140 mA
- Width
- 117 mm
- Depth
- 50 mm
Specifications
- Range Compatibility
- TeSys T LTMR motor controller
- Product Or Component Type
- operator control unit
- Range
- TeSys
- Device Connection
- connection to a LTM R controller, RJ45 rear || connection to a PC, RJ45 front
- Control Button Type
- 10 push-button
- Local Signalling
- 4 LEDs
- Display Type
- Backlit LCD
- Device Short Name
- LTMCU
Documents
Data Sheet
DownloadCAD Models
Trace parts