Motor Management, TeSys T, motor controller, Ethernet/IP, Modbus/TCP, 6 inputs, 3 outputs, 1.35 to 27A, 100 to 240 VAC
LTMR27EFM
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
$1,230.93
1
Payment methods:
A total of 18 Parts In-Stock from 17 Distributors

Environment

Product Certifications
EAC || DNV || BV || C-tick || CCC || ABS || RINA || RMRoS || CSA || NOM || LROS (Lloyds register of shipping) || UL || KERI || GL || ATEX
Mechanical Robustness
vibrations mounted on symmetrical rail1 Gn, 5...300 Hz EN/IEC 60068-2-6 || vibrations plate mounted4 Gn, 5...300 Hz EN/IEC 60068-2-6 || shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27
Ambient Air Temperature For Operation
-20-60 °C
Standards
IACS E10 || UL 508 || IEC 60947-4-1 || EN 60947-4-1 || CSA C22.2 No 14
Ambient Air Temperature For Storage
-40-80 °C
Protective Treatment
12 x 24 hour cycles EN/IEC 60068-2-30 || 48 h EN/IEC 60070-2-11 || TH EN/IEC 60068
Operating Altitude
<= 6561.68 ft (2000 m) without derating
Fire Resistance
650 °C EN/IEC 60695-2-12 || 960 °C UL 94
Ip Degree Of Protection
IP20

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP060308EN_V2
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI100411EN_V2
Eu Rohs Directive
Compliant with Exemptions
Halogen Content Performance
Halogen free plastic parts product

Complementary

Contacts Type And Composition
1 NO + 1 NC fault signal || 3 NO
Height
61 mm
Connection Pitch
5.08 mm
Permissible Power
480 VA AC-15), Ie = 2 A, 500000 cycles output) || 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
Network And Machine Diagnosis Type
event recording || trip context information || phase fault and earth fault trip counters || trip history information || waiting time after overload tripping || fault recording || remaining operating time before overload tripping || starting current and time || motor control command recording || running hours counter/operating time
Pollution Degree
3
Logic Input Number
6
Maximum Operating Rate
1800 cyc/h
Connections - Terminals
control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible with cable end || control circuit connector 1 0.2-2.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 1 0.2-2.5 mm² AWG 24...AWG 14)solid without cable end || control circuit connector 2 0.2-1 mm² AWG 24...AWG 14)flexible with cable end || control circuit connector 2 0.2-1.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 2 0.5-1.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 2 0.2-1 mm² AWG 24...AWG 14)solid without cable end
Input Current
3.1 mA 100 V || 7.5 mA 240 V
Current State 1 Guaranteed
logic input 79...264 V >= 2 mA 25 ms
Net Weight
0.53 kg
[Uimp] Rated Impulse Withstand Voltage
4 kV supply, inputs and outputs EN/IEC 60947-4-1 || 6 kV current or voltage measurement circuit EN/IEC 60947-4-1 || 0.8 kV communication circuit EN/IEC 60947-4-1
Associated Fuse Rating
4 A gG output || 0.5 A gG control circuit
Electromagnetic Compatibility
electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5 || control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 || radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3 || fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 || fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 || voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11 || conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 || temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5 || temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 || control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5
Measurement Accuracy
5...15 % earth fault current internal measurement || 1 % voltage 100...830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 1 % current || 5 % active and reactive power
Current State 0 Guaranteed
logic input 0...40 V <= 15 mA 25 ms
[Ui] Rated Insulation Voltage
690 V EN/IEC 60947-1 || 690 V CSA C22.2 No 14 || 690 V UL 508
Short-Circuit Withstand
100 kA conforming to EN/IEC 60947-4-1
Compatibility Code
LTMR
Protection Type
phase unbalance || earth-leakage protection || thermal protection || reverse polarity protection || power factor variation || overload || load fluctuation || locked rotor || thermal overload protection || phase failure || overload (long time)
Web Services
web server
Width
91 mm
Load Current
5 A 250 V AC logic output || 5 A 30 V DC logic output
Tightening Torque
control circuit 0.5-0.6 N.m flat 3 mm
Overvoltage Category
III
Depth
122.5 mm
Maximum Operating Frequency
2 Hz
Metering Type
average current Iavg || phase current I1, I2, I3 RMS || imbalance current || earth-fault current || temperature

Specifications

Product Or Component Type
motor controller
Product Name
TeSys T
Measurement Current
1.35-27 A
Range
TeSys
Current Consumption
8...62.8 mA
[Us] Rated Supply Voltage
100...240 V AC 50/60 Hz
Communication Port Protocol
Modbus TCP/EtherNet/IP
Bus Type
Ethernet IEEE 802.3 0...159 10...100 Mbit/s, RJ45 2 shielded twisted pairs
Supply Voltage Limits
93.5-264 V AC
Device Application
equipment monitoring and control
Device Short Name
LTMR

Documents

Data Sheet

Download

CAD Models

Trace parts
Trace parts
Download

Related products