Specifications
- Network Frequency
- 50/60 Hz
- Trip Unit Name
- Micrologic 6.2 E-M
- Range Of Product
- ComPact NSX100...250
- [Ue] Rated Operational Voltage
- 690 V AC 50/60 Hz
- Trip Unit Protection Functions
- LSIG
- Network Type
- AC
- Protected Poles Description
- 3t
- Product Or Component Type
- trip unit
- Protection Type
- L : for overload protection (long time) || S : for short time short-circuit protection || I : for instantaneous short-circuit protection || G : for ground fault protection
- Range
- ComPact
- Poles Description
- 3P
- Range Compatibility
- ComPact NSX100 || ComPact NSX160 || ComPact NSX250
- Device Application
- motor
- Trip Unit Technology
- electronic
Contractual warranty
- Warranty
- 18 months
Complementary
- [Tg] Ground-Fault Time Delay Adjustment Range
- 0-0.4 s
- [Ig] Ground-Fault Pick-Up Adjustment Range
- 0.2...1 x In In > 50 A || 0.3...1 x In In = 50 A || 0.6...1 x In In = 25 A || Ig enable on/off
- Thermal Memory
- 20 minutes before and after tripping
- Earth-Leakage Protection
- without
- Ground-Fault Time Delay Adjustment Type -Tg
- adjustable
- Complementary Motor Protection
- stalled rotor || protracted starting time || underload || current unbalance
- Ground-Fault Pick-Up Adjustment Type
- adjustable
- Type Of Measurement
- energy meter
- Long Time Delay Adjustment Type
- adjustable
- Instantaneous Pick-Up Adjustment Type Ii
- fixed
- Zone Selective Interlocking Zsi
- with
- Electrical Data Recording
- maintenance indicators
- [Tr] Long-Time Delay Adjustment Range
- 120-120 s 1.5 x Ir 5 || 6.5-6.5 s 6 x Ir 5 || 5-5 s 7.2 x Ir 5 || 240-240 s 1.5 x Ir 10 || 13.5-13.5 s 6 x Ir 10 || 10-10 s 7.2 x Ir 10 || 480-480 s 1.5 x Ir 20 || 26-26 s 6 x Ir 20 || 20-20 s 7.2 x Ir 20 || 720-720 s 1.5 x Ir 30 || 38-38 s 6 x Ir 30 || 30-30 s 7.2 x Ir 30
- Short-Time Delay Adjustment Type
- fixed
- Instantaneous Pick-Up Adjustment Range
- 1200 A
- Long Time Pick-Up Adjustment Type Ir
- adjustable 9 settings
- Long Time Pick-Up Adjustment Range
- 35...80 A
- [Tsd] Short-Time Delay Adjustment Range
- 0.01-0.01 s
- Motor Tripping Class
- 30 || 20 || 10 || 5
- [Isd] Short-Time Pick-Up Adjustment Range
- 5...13 x Ir
- Display Type
- LCD display
- Short-Time Pick-Up Adjustment Type Isd
- adjustable 9 settings
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP120606EN
- Sustainable Offer Status
- Green Premium product
- California Proposition 65
- WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI120604EN
- Eu Rohs Directive
- Compliant
Environment
- Product Certifications
- CCC || Marine || EAC
- Ambient Air Temperature For Operation
- -25-70 °C
- Standards
- EN/IEC 60947-2 || UL 508
- Ambient Air Temperature For Storage
- -40-85 °C