Earth-leakage add-on protection module VigiPacT, ComPacT NSX 400/630, 200VAC to 440VAC, 30mA to 30A, 3 poles
LV432464
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€400.67
1
Payment methods:
A total of 54 Parts In-Stock from 19 Distributors
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
€346.95

Additional Information

Part Number
LV432464
UNSPSC
41113645
Tariff Code
8536308000
Country of Origin
IT

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP2309055EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI2309055EN
Eu Rohs Directive
Compliant with Exemptions

Specifications

Line Rated Current
400 A || 630 A
Range Of Product
ComPacT NSX400...630 new generation || ComPact NSX400...630
Range Compatibility
ComPacT new generation ComPacT NSX400 new generation circuit breaker || ComPacT new generation ComPacT NSX630 new generation circuit breaker || ComPact ComPact NSX400 circuit breaker || ComPact ComPact NSX630 circuit breaker
Earth-Leakage Protection Class
class A || class AC
Earth-Leakage Sensitivity
0.03 A class A || 0.1 A class A || 0.3 A class A || 0.5 A class A || 1 A class A || 3 A class A || 10 A class AC || 30 A class AC
Product Or Component Type
Vigi add-on
[Δt] Residual Earth-Leakage Time Delay Adjustment
0-0 ms || 60-60 ms || 150-150 ms || 300-300 ms || 500-500 ms || 800-800 ms || 1.2-1.2 s || 4-4 s
Residual Earth-Leakage Sensitity Adjustment Type
adjustable
Poles Description
3P
Device Application
wiring
Residual Earth-Leakage Time Delay Adjustment Type
adjustable
Device Short Name
VigiPacT

Complementary

Network Frequency
50/60 Hz
[Ue] Rated Operational Voltage
200...440 V AC 50/60 Hz IEC 60947-2
Earth-Leakage Protection
with
Network Type
AC
Maximum Breaking Time
800 ms
Overvoltage Category
IV

Environment

Standards
IEC 60947-2
Electrical Shock Protection Class
class II

Documents

Data Sheet

Download

CAD Models

Trace parts
Trace parts
Download