Schneider Electric
LV432895
Circuit breaker, ComPact NSX630H, 70kA/415VAC, MicroLogic 2.3 trip unit 630A, 3 poles 3d
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
€817.77
1
Payment methods:
A total of 7 Parts In-Stock from 10 Distributors
Product Conditions:
Offer with manufacturer lead time
Ships in:On Request
Best price:
€1,256.86
Additional Information
- Part Number
- LV432895
- UNSPSC
- 39121601
- Country of Origin
- FR
Specifications
- Network Frequency
- 50/60 Hz
- Line Rated Current
- 630 A 40 °C
- Trip Unit Name
- Micrologic 2.3
- Range Of Product
- ComPact NSX400...630
- [Ue] Rated Operational Voltage
- 690 V AC 50/60 Hz
- Trip Unit Protection Functions
- LSoI
- Network Type
- AC
- Protected Poles Description
- 3t
- Product Or Component Type
- circuit breaker
- Product Name
- ComPact NSX
- Range
- ComPact
- Control Type
- toggle
- Utilisation Category
- category A
- Mounting Mode
- fixed
- Breaking Capacity
- 85 kA 240 V AC 50/60 Hz UL 508 || 65 kA 480 V AC 50/60 Hz UL 508 || 100 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 65 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 70 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2 || 20 kA 600 V AC 50/60 Hz UL 508 || 20 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
- Suitability For Isolation
- yes EN/IEC 60947-2
- Poles Description
- 3P
- Breaking Capacity Code
- H 70 kA 415 V AC
- Device Application
- distribution
- Device Short Name
- NSX630H
- Trip Unit Technology
- electronic
Contractual warranty
- Warranty
- 18 months
Complementary
- [Ics] Rated Service Breaking Capacity
- 11 kA 525 V AC 50/60 Hz IEC 60947-2 || 10 kA 660/690 V AC 50/60 Hz IEC 60947-2 || 100 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 50 kA 500 V AC 50/60 Hz IEC 60947-2 || 65 kA 440 V AC 50/60 Hz IEC 60947-2 || 70 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Height
- 255 mm
- Thermal Memory
- 20 minutes before and after tripping
- Earth-Leakage Protection
- without
- Mounting Support
- backplate
- Instantaneous Pick-Up Adjustment Range
- 6900 A
- Downside Connection
- front
- Number Of Slots
- 6
- Protection Type
- L : for overload protection (long time) || So : for short time short-circuit protection with fixed delay || I : for instantaneous short-circuit protection
- Long Time Delay Adjustment Type
- fixed
- Instantaneous Pick-Up Adjustment Type Ii
- fixed
- Zone Selective Interlocking Zsi
- without
- Net Weight
- 6.2 kg
- [Tr] Long-Time Delay Adjustment Range
- 16-16 s 6 x Ir
- Electrical Durability
- 2000 cycles 690 V In || 6000 cycles 690 V In/2 || 4000 cycles 440 V In || 8000 cycles 440 V In/2
- Short-Time Delay Adjustment Type
- fixed
- Long Time Pick-Up Adjustment Type Ir
- adjustable 9 settings
- Long Time Pick-Up Adjustment Range
- 250...630 A
- Upside Connection
- front
- [Ui] Rated Insulation Voltage
- 800 V AC 50/60 Hz
- Trip Unit Rating
- 630-630 A 40 °C
- Local Signalling
- for ready to operate flashing LED (green) || for overload LED 105 % Ir (red) || for overload LED 90 % Ir (orange)
- Mechanical Durability
- 15000 cycles
- [Isd] Short-Time Pick-Up Adjustment Range
- 1.5...10 x Ir
- Connection Pitch
- 45 mm
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV
- Width
- 140 mm
- Depth
- 110 mm
- Short-Time Pick-Up Adjustment Type Isd
- adjustable 9 settings
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP120606EN
- Sustainable Offer Status
- Green Premium product
- California Proposition 65
- WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI120604EN
- Eu Rohs Directive
- Compliant
Environment
- Product Certifications
- CCC || EAC || Marine
- Ik Degree Of Protection
- IK07 IEC 62262
- Ambient Air Temperature For Operation
- -25-70 °C
- Standards
- EN/IEC 60947
- Ip Degree Of Protection
- IP40 conforming to IEC 60529
- Electrical Shock Protection Class
- class II
- Pollution Degree
- 3 IEC 60664-1
- Ambient Air Temperature For Storage
- -50-85 °C
- Relative Humidity
- 0-95 %
- Operating Altitude
- 0...6561.68 ft (0...2000 m) without derating || 2000 m...5000 m with derating
- Overvoltage Category
- class II
CAD Models
traceparts
Download