Circuit breaker frame, MasterPact MTZ2 25H3, 2500A, 150kA/440VAC 50/60Hz (Icu), 3P, drawout, without control unit
LV848302
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
Send request for price

Additional Information

Part Number
LV848302
UNSPSC
39121601

Specifications

Network Frequency
50/60 Hz
Network Type
AC
Breaking Capacity Code
H3
Product Or Component Type
circuit breaker
Product Name
MasterPact MTZ2
Range
Masterpact
Utilisation Category
category B
Suitability For Isolation
yes IEC 60947-2
Poles Description
3P
Device Application
protection
Device Short Name
MTZ2 25 H3

Complementary

[Ics] Rated Service Breaking Capacity
150 kA 220/415 V AC 50/60 Hz IEC 60947-2 || 150 kA 440 V AC 50/60 Hz IEC 60947-2 || 130 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 100 kA 660/690 V AC 50/60 Hz IEC 60947-2
Line Rated Current
2500 A 40 °C
Connection Pitch
115 mm
[Ue] Rated Operational Voltage
440 V AC 50/60 Hz IEC 60947-2
Mounting Support
rails || base plate
Circuit Breaker Ct Rating
2500 A
Maximum Breaking Time
25-25 ms
Depth
drawout circuit breaker without chassis 300 mm || drawout circuit breaker with chassis 403 mm
Control Type
push-button
Maximum Closing Response Time
70 ms
Mounting Mode
drawout
Breaking Capacity
150 kA Icu 220/415 V AC 50/60 Hz IEC 60947-2 || 150 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 130 kA Icu 500/525 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
[Icm] Rated Short-Circuit Making Capacity
330 kA 220/415 V AC 50/60 Hz || 330 kA 440 V AC 50/60 Hz || 286 kA 500/525 V AC 50/60 Hz || 220 kA 660/690 V AC 50/60 Hz
Electrical Durability
1250 cycles 440 V AC 50/60 Hz IEC 60947-2 || 1250 cycles 690 V AC 50/60 Hz IEC 60947-2
[Ui] Rated Insulation Voltage
1000 V AC 50/60 Hz IEC 60947-2
Mechanical Durability
20000 cycles with periodic preventive maintenance IEC 60947-2
Height
drawout circuit breaker without chassis 300 mm || drawout circuit breaker with chassis 439 mm
Width
drawout circuit breaker without chassis 378 mm || drawout circuit breaker with chassis 441 mm
Integral Instant Protection
135-165 kA
[Uimp] Rated Impulse Withstand Voltage
12 kVIEC 60947-2
[Icw] Rated Short-Time Withstand Current
66 kA 0.5 s IEC 60947-2 || 66 kA 1 s IEC 60947-2 || 66 kA 3 s IEC 60947-2

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1607009EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI1607009EN
Eu Rohs Directive
Compliant

Environment

Product Certifications
ASEFA
Ambient Air Temperature For Operation
-25-70 °C
Standards
IEC 60947-2 || IEC 60364-8-1
Pollution Degree
3 IEC 60947-1
Ambient Air Temperature For Storage
-40-85 °C

CAD Models

Trace parts
Trace parts
Download

Related products