Reversing ultra compact starter, TeSys Hybrid, 3P, 500VAC, 3kW at 400V, 110 to 230VAC, Spring terminal
LZ2H6X53FU
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
€86.66

Additional Information

Part Number
LZ2H6X53FU
UNSPSC
39121521
Tariff Code
8537106000
Country of Origin
DE

Specifications

[Uc] Control Circuit Voltage
110...230 V AC 50/60 Hz
[Ue] Rated Operational Voltage
500 V AC
Thermal Protection Adjustment Range
1.5-9 A
Product Or Component Type
reversing ultra-compact starter
Product Name
TeSys Hybrid
Thermal Overload Class
class 10A IEC 60947-4-2
Motor Power Kw
1.5 kW 220 V AC 0.65 || 1.5 kW 230 V AC 0.65 || 2.2 kW 380 V AC 0.65 || 3 kW 400 V AC 0.65 || 3 kW 415 V AC 0.65 || 3 kW 440 V AC 0.65 || 3 kW 500 V AC 0.65
Range
TeSys
Motor Starter Type
direct on line
[Ie] Rated Operational Current
6.5 A 500 V AC-53A || 9 A 500 V AC-51 || 4.5 A 500 V AC-53A mounting side by side || 6 A 500 V AC-51 mounting side by side
Poles Description
3P
Maximum Horse Power Rating
1 hp 200 V AC || 1.5 hp 230 V AC || 3 hp 460 V AC
Device Short Name
LZ2H

Complementary

Height
99 mm
Reset
manual || automatic reset || electrical reset
Standards
IEC 60947-4-2 || UL 60947-4-1
Mounting Support
DIN rail
Pollution Degree
2
Net Weight
212 g
[Uimp] Rated Impulse Withstand Voltage
4 kV
Connections - Terminals
spring clamp terminals 1 0.2-2.5 mm² rigid || spring clamp terminals 1 0.25-2.5 mm² flexible - with cable end || spring clamp terminals 1 0.2-2.5 mm² flexible - without cable end
Current Consumption
<= 4 mA 110...230 V AC
[Ui] Rated Insulation Voltage
500 V AC 50/60 Hz
Mounting Mode
by clips
Maximum Operating Rate
120 cyc/mn AC-51 50 % || 6 cyc/mn AC-53A 50 %
Auxiliary Contact Composition
1 C/O fault signalling
Control Circuit Voltage Limits
85...253 V AC
Certifications
CE || cULus
Width
22.5 mm
Depth
114.5 mm
Electrical Durability
30 Mcycles

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1509013EN
Sustainable Offer Status
Green Premium product
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Circularity Profile
ENVEOLI1509013EN
Eu Rohs Directive
Compliant

Environment

Ambient Air Temperature For Operation
-25-30 °C without derating || 30-70 °C with derating
Ambient Air Temperature For Storage
-40-80 °C
Protective Treatment
TC
Ip Degree Of Protection
IP20

CAD Models

Trace parts
Trace parts
Download

Related products