Specifications
- [Uc] Control Circuit Voltage
- 110...230 V AC 50/60 Hz
- [Ue] Rated Operational Voltage
- 500 V AC
- Thermal Protection Adjustment Range
- 1.5-9 A
- Product Or Component Type
- reversing ultra-compact starter
- Product Name
- TeSys Hybrid
- Thermal Overload Class
- class 10A IEC 60947-4-2
- Motor Power Kw
- 1.5 kW 220 V AC 0.65 || 1.5 kW 230 V AC 0.65 || 2.2 kW 380 V AC 0.65 || 3 kW 400 V AC 0.65 || 3 kW 415 V AC 0.65 || 3 kW 440 V AC 0.65 || 3 kW 500 V AC 0.65
- Range
- TeSys
- Motor Starter Type
- direct on line
- [Ie] Rated Operational Current
- 6.5 A 500 V AC-53A || 9 A 500 V AC-51 || 4.5 A 500 V AC-53A mounting side by side || 6 A 500 V AC-51 mounting side by side
- Poles Description
- 3P
- Safety Reliability Data
- SFF = 99 % stop function || SFF = 99 % motor protection || MTTFd = 289 years stop function || MTTFd = 273 years motor protection || PFHd = 6.82E-9 1/h stop function
- Maximum Horse Power Rating
- 1 hp 200 V AC || 1.5 hp 230 V AC || 3 hp 460 V AC
- Device Short Name
- LZ8H
- Safety Level
- SIL 3 IEC 61508-1 stop function || PL = e ISO 13849-1 stop function || SIL 2 IEC 61508-1 motor protection
Complementary
- Height
- 99 mm
- Reset
- manual || electrical reset
- Standards
- UL 60947-4-1 || IEC 60947-4-2
- Mounting Support
- DIN rail
- Pollution Degree
- 2
- Net Weight
- 212 g
- [Uimp] Rated Impulse Withstand Voltage
- 4 kV
- Connections - Terminals
- spring clamp terminals 1 0.2-2.5 mm² rigid || spring clamp terminals 1 0.25-2.5 mm² flexible - with cable end || spring clamp terminals 1 0.2-2.5 mm² flexible - without cable end
- Current Consumption
- <= 4 mA 110...230 V AC
- [Ui] Rated Insulation Voltage
- 500 V AC 50/60 Hz
- Mounting Mode
- by clips
- Maximum Operating Rate
- 120 cyc/mn AC-51 50 % || 6 cyc/mn AC-53A 50 %
- Auxiliary Contact Composition
- 1 C/O fault signalling
- Control Circuit Voltage Limits
- 85...253 V AC
- Certifications
- cULus || CE || ATEX as associated device for motor protection in zones 1 and 21
- Width
- 22.5 mm
- Depth
- 114.5 mm
- Electrical Durability
- 30 Mcycles
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1509013EN
- Sustainable Offer Status
- Green Premium product
- Toxic Heavy Metal Free
- Yes
- Reach Regulation
- Free of Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
- Reach Free Of Svhc
- Yes
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- X
- Circularity Profile
- ENVEOLI1509013EN
- Eu Rohs Directive
- Compliant
Environment
- Ambient Air Temperature For Operation
- -25-30 °C without derating || 30-70 °C with derating
- Ambient Air Temperature For Storage
- -40-80 °C
- Protective Treatment
- TC
- Ip Degree Of Protection
- IP20