Miniature circuit breaker (MCB), Multi9 C60H, 4P, 3A, C curve, 15kA (IEC/EN 60947-2)
M9F14403
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
Send request for price

Additional Information

Part Number
M9F14403
UNSPSC
39121603
Tariff Code
8536200020
Country of Origin
FR

Specifications

Line Rated Current
3 A 50 °C EN/IEC 60947-2
Curve Code
C
Number Of Protected Poles
4
Network Type
AC || DC
Standards
EN/IEC 60947-2
Product Certifications
EAC || CCC
Product Or Component Type
miniature circuit-breaker
Product Name
Multi9 C60
Utilisation Category
category A EN/IEC 60947-2
Range
Multi9
Breaking Capacity
50 kA Icu <= 250 V DC EN/IEC 60947-2 || 30 kA Icu 240 V AC 50/60 Hz between phases EN/IEC 60947-2 || 15 kA Icu 415 V AC 50/60 Hz between phases EN/IEC 60947-2 || 10 kA Icu 440 V AC 50/60 Hz between phases EN/IEC 60947-2
Suitability For Isolation
yes EN/IEC 60947-2
Poles Description
4P
Device Application
distribution
Device Short Name
C60H
Trip Unit Technology
thermal-magnetic

Complementary

Network Frequency
50/60 Hz
[Ics] Rated Service Breaking Capacity
15 kA 50 % EN/IEC 60947-2 - 240 V AC 50/60 Hz || 7.5 kA 50 % EN/IEC 60947-2 - 415 V AC 50/60 Hz || 5 kA 50 % EN/IEC 60947-2 - 440 V AC 50/60 Hz || 50 kA 100 % EN/IEC 60947-2 - <= 250 V DC
Height
81 mm
Contact Position Indicator
yes
Earth-Leakage Protection
separate block
Mounting Support
DIN rail
9 Mm Pitches
8
Net Weight
0.48 kg
Wire Stripping Length
14 mm top or bottom
Control Type
toggle
Connections - Terminals
tunnel type terminal top or bottom) 1-25 mm² - rigid || tunnel type terminal top or bottom) 1-25 mm² - flexible || tunnel type terminal top or bottom) 1-25 mm² - flexible with ferrule
[Ui] Rated Insulation Voltage
500 V AC 50/60 Hz EN/IEC 60947-2
Mounting Mode
clip-on
Electrical Durability
10000 cycles
Mechanical Durability
20000 cycles
Local Signalling
ON/OFF indication
[Uimp] Rated Impulse Withstand Voltage
6 kVEN/IEC 60947-2
Color
Gray
Width
72 mm
Provision For Padlocking
padlockable
Depth
72 mm
Tightening Torque
2-2 N.m top or bottom
Magnetic Tripping Limit
8.5 x In +/- 20 % AC || 12 x In +/- 20 % DC
[Ue] Rated Operational Voltage
240 V AC 50/60 Hz between phases || 415 V AC 50/60 Hz between phases || 440 V AC 50/60 Hz between phases || <= 250 V DC

Environment

Ambient Air Temperature For Operation
-30-70 °C
Tropicalisation
2 IEC 60068-1
Ip Degree Of Protection
IP20 conforming to IEC 60529 || IP40 (modular enclosure) conforming to IEC 60529
Pollution Degree
3 EN/IEC 60947-2
Ambient Air Temperature For Storage
-40-80 °C
Relative Humidity
95-95 % 55-55 °C
Overvoltage Category
IV
Heat Dissipation
8.8-8.8 W 415 V - 3 A

Documents

Data Sheet

Download