Schneider Electric

METSEEM408016

EM4000 multi-circuit energy meter, 24 x 80 mA inputs, 120V control power 60 Hz
METSEEM408016
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Offer Sustainability

China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Rohs Exemption Information
Yes
Mercury Free
Yes
Toxic Heavy Metal Free
Yes
Eu Rohs Directive
Compliant
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.

Environment

Ambient Air Temperature For Operation
-40-70 °C
Height
33.5 cm
Pollution Degree
2
Mounting Mode
wall mount
Ambient Air Temperature For Storage
-40-70 °C
Relative Humidity
90-90 % 40-40 °C
Standards
IEC 6100-4-5 || ICES-003 || FCC Part 15 class B || CSA C22.2 No 61010-1 || EN 55022 || ANSI/TIA-968-A : 2002 || CSA C22.2 No 61010-1-4
Device Mounting
wall mounted
Product Certifications
UL
Width
30.5 cm
Enclosure Type
NEMA type 1
Depth
5.5 cm
Net Weight
4 kg
Type Of Installation
enclosed outdoor || indoor installation
Operating Altitude
<= 9842.52 ft (3000 m)

Complementary

Communication Port Support
RJ45 ETHERNET || RS485
Measurement Accuracy
+/- 0.5 % of the measuring range
Measurement Voltage
80-480 V without PTs || 480-999000 V with external PTs
Sampling Rate
256 samples/cycle
Communication Port Protocol
BACnet IP || FTP || HTTP || Modbus TCP/IP || SNTP
Analogue Input Type
solid core CT 80 mA24 x single pole || solid core CT 80 mA12 x single phase || solid core CT 80 mA8 x three phase
Display Type
Backlit LCD
Communication Of Data
negative active energy || positive active energy || voltage || positive reactive energy || apparent energy || negative reactive energy
Number Of Inputs
2 pulse
Messages Display Capacity
2 lines of 16 characters

Specifications

Network Frequency
60 Hz
Energy Management
sub billing and cost allocation || billing analysis
[Us] Rated Supply Voltage
120 V AC 60 Hz
Power Quality Analysis
compliance monitoring
Type Of Measurement
current per phase, rms || negative active energy || voltage per phase, rms || negative reactive energy || apparent energy || pulse count || active and reactive power || apparent power || positive active energy || positive reactive energy
Power Monitoring
basic instrumentation
Product Or Component Type
multi-circuit energy meter
Product Name
PowerLogic EM4000
Device Application
sub billing
Device Short Name
EM4080
Range
PowerLogic

Documents