Schneider Electric
METSEION93130
PowerLogic™ ION9000 meter, LVDC, DIN mount, Low Voltage input current, no display, HW kit
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Product Conditions:
Offer with manufacturer lead time
Ships in:On Request
Best price:
€4,065.95
Additional Information
- Part Number
- METSEION93130
- UNSPSC
- 41113708
- Tariff Code
- 9030840000
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1801009EN
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- X
- Circularity Profile
- ENVEOLI1801009EN
- Eu Rohs Directive
- Compliant with Exemptions
Complementary
- [Us] Rated Supply Voltage
- 20...60 V DC +/- 10 %
- Communication Port Support
- 2 RS485 removable screw terminal block
- Power Quality Analysis
- EN 50160 compliance checking || IEEE 519 harmonic limit || IEC 61000-4-30 class A compliance reporting || IEEE 519 compliance reporting || waveform capture || total demand distortion || total harmonic distortion || up to the 63rd harmonic || up to the 127th harmonic with software || disturbance direction detection || dip, swell and transient || half cycle data acquisition || transient detection (20 µs)
- Height
- 160 mm
- Measurement Voltage
- 57-400 V AC 42...69 Hz between phase and neutral || 100-690 V AC 42...69 Hz between phases
- Sampling Rate
- 1024 samples/cycle
- Memory Capacity
- 2 GB
- Number Of Outputs
- 4 digital || 2 form C relay
- Type Of Measurement
- voltage sags and swells || current sags and swells || voltage || current || frequency || active and reactive power total || apparent power total || active and reactive power per phase || apparent power per phase || power factor total || power factor per phase || active and reactive energy || apparent energy || harmonic distorsion (I THD & U THD)
- Communication Port Protocol
- Modbus RTU 2400...115200 bps - 2-wire || ION 2400...115200 bps - 2-wire || DNP3 2400...115200 bps - 2-wire || Modbus TCP 10/100 Mbit/s || ION TCP 10/100 Mbit/s || DNP3 TCP 10/100 Mbit/s || IEC 61850 || Ethernet Modbus TCP/IP daisy chain 10/100 Mbit/s || DHCP || DNS || DLMS
- Frequency Measurement Range
- 20-450 Hz
- Communication Service
- compliant reports || power quality summary || energy report || EcoStruxure Power Events Analysis || SMTP e-mail notification || SNMP
- Ride-Through Time
- 500 ms 60 V DC typical
- Port Ethernet
- 10/100BASE-TX 2 RJ45
- Power Consumption In Va
- 15 W 20...60 V DC
- Net Weight
- 1.5 kg
- Tamperproof Of Settings
- protected by sealable cover
- Electrical Insulation Class
- class III EN/IEC 62052-11
- Number Of Inputs
- 8 digital 30 V AC/60 V DC
- Time Synchronisation Protocol
- GPS || IRIG-B || NTP || SNTP || PTP
- Measurement Accuracy
- voltage +/- 0.1 % || current +/- 0.1 %
- Ethernet Service
- DHCP client || Device Profile Web Services (DPWS) || Rapid Scanning Tree Protocol (RSTP) || FTP/HTTP/HTTPS
- Mounting Support
- DIN rail
- Communication Gateway
- Ethernet/serial
- Poles Description
- 3P + N + E
- Data Recording
- time stamping || min/max of instantaneous values || user-definable data logs || continuous logging or snapshot || trending/forecasting || event logs || alarm logs || configuration change || power outage || user login/logout || data logs || GPS synchronisation || sequence of event recording
- Cybersecurity
- Syslog protocol support || robust security logs || port hardening || enable/disable communication ports || hardware metrology lock
- Isolation Voltage
- III400-690 V conforming to EN 61010-1:ed. 3 || III347-600 V conforming to UL 61010-1:ed. 3 || III347-600 V conforming to CSA C22.2 No 61010-1:ed. 3
- Analogue Input Type
- voltage (impedance 5 MOhm) || split core current transducer (impedance 200 kOhm)5 x
- Web Services
- viewing of captured waveform || web page || pass/fail report for IEEE 519 || pass/fail report for EN 50160 || ITIC (CBEMA) curve || SEMI curve || NEMA motor derating curve || alarm notification by e-mail || TLS 1.2 || push historical data via mail
- Width
- 160 mm
- Display Type
- Without Display
- Depth
- 135.3 mm
- Accuracy Class
- class 0.1S active energy IEC 62053-22 || class 0.1 active energy IEC 61557-12 || class 0.1 active energy ANSI C12.20 || class 0.5S reactive energy IEC 62053-24 || class 0.1 current IEC 61557-12 || class 0.1 voltage IEC 61557-12 || class 0.1 active power IEC 61557-12 || class 0.5 power factor IEC 61557-12
- Maximum Power Consumption In Va
- 38 W 20...60 V DC
Specifications
- Product Or Component Type
- energy and power quality meter
- Range
- PowerLogic
- Device Application
- power monitoring || WAGES metering || Net metering || medium voltage || high voltage
- Device Short Name
- ION93030
- Metering Type
- demand current I1, I2, I3, I4, I5 || peak demand currents || demand power P, Q, S || peak demand power PM, QM, SM || calculated active and reactive energy (+/- W.h, +/- VAR.h)
Environment
- Ambient Air Temperature For Operation
- -25-70 °C
- Standards
- ANSI C12.20 || ANSI C37.90.1 || IEC 61000-4-15 || IEC 61000-4-30 || IEC 61010-1 || IEC 61326-1 || IEC 61557-12 || IEC 61850 || IEC 62052-11 || IEC 62052-31 || IEC 62053-22 || IEC 62053-23 || IEC 62053-24 || IEC 62586 || UL 61010-1
- Degree Of Protection
- UL type 12, front
- Electromagnetic Compatibility
- EMC immunity conforming to IEC 62052-11 || EMC immunity conforming to IEC 61326-1 || EMC immunity conforming to IEC 61000-6-5 || electrostatic discharge immunity test conforming to IEC 61000-4-2 || immunity to radiated fields conforming to IEC 61000-4-3 || immunity to fast transients conforming to IEC 61000-4-4 || surge immunity test conforming to IEC 61000-4-5 || immunity to conducted disturbances conforming to IEC 61000-4-6 || immunity to magnetic fields at network frequency conforming to IEC 61000-4-8 || immunity to conducted disturbances - test level: 2...150 kHz conforming to CLC/TR 50579 || voltage dips and interruptions immunity test conforming to IEC 61000-4-11 || immunity to impulse waves conforming to IEC 61000-4-12 || conducted and radiated emissions conforming to EN 55011 || conducted and radiated emissions class B conforming to EN 55032 || conducted and radiated emissions class B conforming to FCC part 15 || conducted and radiated emissions class B conforming to ICES-003 || surge withstand conforming to ANSI C37.90.1 || surge withstand conforming to IEEE C37.90.1
- Ambient Air Temperature For Storage
- -40-85 °C
- Relative Humidity
- 5-95 %
- Quality Labels
- ISO 9001 || ISO 14000
- Ip Degree Of Protection
- front IP65 || rear IP30
- Operating Altitude
- 0...9842.52 ft (0...3000 m)
- Installation Category
- III
Documents
Data Sheet
DownloadOther Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther