PKA36060CU43A

Circuit breaker, PowerPacT P, 600A, 3 pole, 600VAC, 100kA, I-Line, Micrologic 5.0A, 100%, ABC
PKA36060CU43A
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up

Environment

Ambient Air Temperature For Operation
-2-70 °C
Standards
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Product Certifications
UL || CSA || NOM
Ip Degree Of Protection
front cover IP40
Pollution Degree
3 IEC 60947-1
Ambient Air Temperature For Storage
-50-85 °C
Quality Labels
CE
Operating Altitude
< 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP2206033EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI2206033EN
Eu Rohs Directive
Compliant with Exemptions

Complementary

Mounting Mode
I-Line bracket)
Network Frequency
50/60 Hz
Terminal Identifier
AL800M23K
[Ics] Rated Service Breaking Capacity
25 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
Trip Unit Technology
electronic, ammeter, MicroLogic 5.0 A, LSI
Trip Unit Name
MicroLogic 5.0 A
Height
12.86 in
[Ue] Rated Operational Voltage
600 V AC 50/60 Hz UL 489
Tightening Torque
50-50 N.m 95-240 mm² (3 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
Mounting Support
bracket
Breaking Capacity Code
K
Local Signalling
overload 1 trip indicator green) || 1 trip indicator green) || trip causes 1 trip indicator green)
Number Of Slots
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Electrical Connection
I-Line connection, line || lugs, load
Mounting Height
9 in
Net Weight
32 lb(US)
[Uimp] Rated Impulse Withstand Voltage
8 kV IEC 60947-2
Control Type
toggle
Circuit Breaker Application
HACR rated
Wire Stripping Length
25 mm
Line Rated Current
600-600 A
Utilisation Category
category A
Long Time Pick-Up Adjustment Range
0.4...1 x Ir
Continuous Current Rating
100 %
Breaking Capacity
AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 50 kA 480 V AC 50/60 Hz UL 489 || AIR 50 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
[Ui] Rated Insulation Voltage
750 V IEC 60947-2
Suitability For Isolation
yes IEC 60947-2
Poles Description
3P
Quantity Per Set
1
Awg Gauge
3 x AWG 3/0...500 kcmil aluminium/copper
Width
8.27 in
Depth
8.05 in
Phase Connection
ABC

Specifications

Product Or Component Type
circuit breaker
Product Name
PowerPact P
Range
PowerPact
Device Application
distribution

Documents

Data Sheet

Download