QBP22100TM
Circuit breaker, PowerPacT Q, 100A, 2 pole, 240VAC, 10kA, lugs, thermal magnetic, 80%, bottom of panel
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Environment
- Ambient Air Temperature For Operation
- 40-70 °C
- Standards
- UL || CSA || NEMA || NOM-003-SCFI-2000
- Product Certifications
- UL || CSA || NOM
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1406032EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- N/A
- Eu Rohs Directive
- Compliant with Exemptions
- Halogen Content Performance
- Halogen free product
Complementary
- Mounting Mode
- unit mount lug)
- Network Frequency
- 50/60 Hz
- Trip Unit Technology
- thermal-magnetic
- Height
- 6.47 in
- [Ue] Rated Operational Voltage
- 240 V AC 50/60 Hz UL
- Tightening Torque
- 28-28 N.m 25-150 mm² (AWG 4...300 kcmil)
- Mounting Support
- lug
- Breaking Capacity Code
- B
- Magnetic Tripping Current
- 2400-2400 A
- Local Signalling
- 1 trip indicator green)
- Electrical Connection
- terminal nut, line || lugs, load
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV UL
- Magnetic Hold Current
- 1200 A
- Control Type
- operating handle
- Circuit Breaker Application
- HACR rated
- Wire Stripping Length
- 22 mm
- Utilisation Category
- category A
- Line Rated Current
- 100-100 A
- Continuous Current Rating
- 80 %
- Breaking Capacity
- 10 kA 120/208 V AC 50/60 Hz UL || 10 kA 240 V AC 50/60 Hz UL
- Mechanical Durability
- 1000 cycles loaded || 5000 cycles no load
- Poles Description
- 2P
- Line Rated Current
- 100 A
- Width
- 3.00 in
- Depth
- 3.93 in
Specifications
- Product Or Component Type
- circuit breaker
- Product Name
- PowerPact Q
- Range
- PowerPact
- Device Application
- distribution