QDM32125TN
Circuit breaker, PowerPacT Q, 125A, 3 pole, 240VAC, 25kA, lugs, thermal magnetic, 80%, top of panel
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Environment
- Ambient Air Temperature For Operation
- 40-70 °C
- Standards
- UL || CSA || NEMA || NOM-003-SCFI-2000
- Product Certifications
- UL || CSA || NOM
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- N/A
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1406032EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Eu Rohs Directive
- Compliant with Exemptions
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Halogen Content Performance
- Halogen free product
Complementary
- Circuit Breaker Application
- HACR rated
- Mounting Mode
- unit mount lug)
- Network Frequency
- 50/60 Hz
- Wire Stripping Length
- 22 mm
- Utilisation Category
- category A
- Line Rated Current
- 125-125 A
- Trip Unit Technology
- thermal-magnetic
- Height
- 6.47 in
- Continuous Current Rating
- 80 %
- Breaking Capacity
- 25 kA 120/208 V AC 50/60 Hz UL || 25 kA 240 V AC 50/60 Hz UL
- Mechanical Durability
- 1000 cycles loaded || 5000 cycles no load
- [Ue] Rated Operational Voltage
- 240 V AC 50/60 Hz UL
- Tightening Torque
- 28-28 N.m 25-150 mm² (AWG 4...300 kcmil)
- Mounting Support
- lug
- Breaking Capacity Code
- D
- Magnetic Tripping Current
- 2400-2400 A
- Poles Description
- 3P
- Local Signalling
- 1 trip indicator green)
- Line Rated Current
- 125 A
- Width
- 4.5 in
- Electrical Connection
- lugs, line || terminal nut, load
- Depth
- 3.93 in
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV UL
- Magnetic Hold Current
- 1200 A
- Control Type
- operating handle
Specifications
- Product Or Component Type
- circuit breaker
- Product Name
- PowerPact Q
- Device Application
- distribution
- Range
- PowerPact