arc protection relay, PowerLogic A125
REL52900
REL52900
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Complementary

Connections - Terminals
removable screw terminal block
Device Mounting
flush || DIN rail
Number Of Outputs
2 binary || 1 relay || 1 IGBT || 2 control relay
Mounting Support
panel
Discrete Input Voltage
48...240 V AC/DC 250 V)
Type Of Measurement
arc
Display Type
LED 11
Output Current Limits
20 mA 24 V DC
Control And Monitoring Type
switchgear internal arc detection
Depth
total 126 mm
Width
total 70 mm
Height
total 135 mm
Net Weight
0.9 kg
[Us] Rated Supply Voltage
24...240 V AC/DC

Specifications

Range Of Product
Easergy ARC
Protection Type
arc suppression 50ARC
Relay Application
arc flash
Product Or Component Type
arc fault detection device
Product Name
PowerLogic Arc
Range
PowerLogic
Number Of Inputs
3 binary || 1 binary current input || 4 arc sensor || 1 digital
Protection Type
arc suppression
Device Short Name
V125

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1803007
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
China Rohs Regulation
X
Circularity Profile
ENVEOLI1803007
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Environment

Mechanical Robustness
vibrations class 2) IEC 60255-21-1 || shocks class 2) IEC 60255-21-2 || earthquakes criteria A) level 2 IEC 60255-21-3 || vibrations Fc) IEC 60068-2-6 || shocks Ea) IEC 60068-2-27
Ambient Air Temperature For Operation
-40-65 °C
Standards
EN/IEC 60255-1 || EN 60255-27
Environmental Characteristic
exposure to dry heat Bd EN/IEC 60068-2-2 || exposure to cold Ad EN/IEC 60068-2-1 || exposure to damp heat in service Db EN/IEC 60068-2-30 || exposure to damp heat in service Cab EN/IEC 60068-2-78 || temperature variation Nb IEC 60068-2-14
Ip Degree Of Protection
IP20 conforming to IEC 60529
Electromagnetic Compatibility
emission tests IEC/EN 60255-26 ed. 3 || emission tests class A EN 55022 || emission tests CISPR 22 || emission tests class A EN 55011 || emission tests IEC 60255-25 || emission tests CISPR 11 || EMC immunity A IEC/EN 60255-26 ed. 3 || damped oscillatory wave EN/IEC 61000-4-18 || electrostatic discharge level 4 EN/IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 EN/IEC 61000-4-3 || electrical fast transient level 4 EN/IEC 61000-4-4 || surge immunity test level 3 EN/IEC 61000-4-5 || immunity to conducted interference caused by radio-electrical fields level 3 EN/IEC 61000-4-6 || immunity to magnetic fields EN/IEC 61000-4-8 || immunity to magnetic fields level 5 EN/IEC 61000-4-9 || immunity to voltage dips power lines (DC) EN/IEC 61000-4-29 || immunity to voltage dips EN/IEC 61000-4-11 || immunity to ripple EN/IEC 61000-4-17
Ambient Air Temperature For Storage
-40-80 °C
Relative Humidity
0-95 % without condensation
Protective Treatment
conformal coating
Operating Altitude
<= 6561.68 ft (2000 m)

Documents

Data Sheet

Download