RM35JA32MR

current control relay, Harmony Control Relays, 5A, 2CO, 0.15…15A, 24…240V AC DC
RM35JA32MR
RM35JA32MR
RM35JA32MR
RM35JA32MR
RM35JA32MR
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up

Specifications

Minimum Switching Current
10 mA 5 V DC
Maximum Switching Current
8 A AC
Range Of Product
Harmony Control Relays
Measurement Range
0.15...1.5 A E1-M terminals || 0.5...5 A E2-M terminals || 1.5...15 A E3-M terminals || 150 mA...15 A current AC/DC 50/60 Hz
Switching Capacity In Va
2000 VA
Product Or Component Type
current control relay
Utilisation Category
AC-15 IEC 60947-5-1 || DC-13 IEC 60947-5-1 || AC-1 IEC 60947-4-1 || DC-1 IEC 60947-4-1
Relay Name
RM35JA
Contacts Type And Composition
2 C/O
Relay Type
current control relay
Time Delay Type
adjustable 0.1...30 s, +/- 10 % of the full scale value on crossing the threshold Tt
Relay Monitored Parameters
overcurrent or undercurrent in window mode || overcurrent or undercurrent detection
Maximum Power Consumption In Va
3.5 VA

Complementary

[Us] Rated Supply Voltage
24...240 V AC/DC 50/60 Hz +/- 10 %
Safety Reliability Data
MTTFd = 296.8 years || B10d = 270000
Maximum Measuring Cycle
100 ms measurement cycle as true rms value
Switching Threshold Drift
<= 0.05 % per degree centigrade depending permissible ambient air temperature || <= 1 % within the supply voltage range
Control Circuit Voltage Limits
15 % + 10 % Un
Hysteresis
5-50 % adjustable threshold setting || 3-3 % fixed full scale for window mode
Insulation Resistance
> 100 MOhm 500 V DC IEC 60255-27
Measurement Error
< 1 % over the whole range with voltage variation || 0.05 %/°C with temperature variation
Internal Input Resistance
0.015 Ohm || 0.005 Ohm || 0.05 Ohm
Output Contacts
2 C/O
Contacts Material
cadmium free
Response Time
<= 500 ms (on crossing the threshold)
Net Weight
0.12 kg
Threshold Setting
10...100 %
Maximum Switching Voltage
250 V AC
Reset Time
1500 ms at maximum voltage
Connections - Terminals
screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end || screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end
Overvoltage Category
III IEC 60664-1 || III UL 508
Insulation
between supply and measurement
Time Delay Drift
<= 0.05 % per degree centigrade depending permissible ambient air temperature || <= 1 % within the supply voltage range
Setting Accuracy Of Time Delay
10 P
Supply Voltage Limits
20.4-264 V AC/DC
Mounting Support
35 mm DIN rail conforming to IEC 60715
Nominal Output Current
8 A
Local Signalling
for relay ON LED (yellow) || for power ON LED (green)
Mechanical Durability
10000000 cycles
Housing Material
self-extinguishing plastic
Resistance Across Terminals
0.005 Ohm E3-M terminals || 0.015 Ohm E2-M terminals || 0.05 Ohm E1-M terminals
Width
35 mm
Tightening Torque
0.6-1 N.m IEC 60947-1
Maximum Power Consumption In W
1.5 W DC
Electrical Durability
100000 cycles
Run-Up Delay At Power-Up
0.3 s
Repeat Accuracy
+/- 0.5 % input and measurement circuit || +/- 2 % time delay
Setting Accuracy Of The Switching Threshold
+/- 10 % of the full scale

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1504008EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Circularity Profile
ENVEOLI1504008EN
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Environment

Product Certifications
CE || GL || CCC || EAC || RCM || UL || CSA
Standards
IEC 60255-1
Immunity To Microbreaks
50 ms
Dielectric Test Voltage
2.5 kV AC 50 Hz, 1 min IEC 60255-27
Electromagnetic Compatibility
immunity for residential, commercial and light-industrial environments conforming to IEC 61000-6-1 || immunity for industrial environments conforming to IEC 61000-6-2 || emission standard for industrial environments conforming to IEC 61000-6-4 || electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2 || electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 conforming to IEC 61000-4-3 || electrical fast transient/burst immunity test - test level: 4 kV level 4 (direct) conforming to IEC 61000-4-4 || electrical fast transient/burst immunity test - test level: 2 kV level 4 (capacitive coupling) conforming to IEC 61000-4-4 || surge immunity test - test level: 4 kV level 4 (common mode) conforming to IEC 61000-4-5 || surge immunity test - test level: 2 kV level 4 (differential mode) conforming to IEC 61000-4-5 || conducted and radiated emissions class B group 1 conforming to CISPR 11 || conducted and radiated emissions class B conforming to CISPR 22 || emission standard for residential, commercial and light-industrial environments (except radiated emission) conforming to IEC 61000-6-3
Shock Resistance
15 gn 11 ms) not in operation IEC 60068-2-27 || 5 gn 11 ms) in operation IEC 60068-2-27
Ambient Air Temperature For Operation
-20-50 °C 60 Hz || -20-60 °C 50 Hz
Vibration Resistance
0.075 mm 10-58.1 Hz) not in operation IEC 60068-2-6 || 1 gn 10-58.1 Hz) not in operation IEC 60068-2-6 || 0.035 mm 58.1-150 Hz) in operation IEC 60068-2-6 || 0.5 gn 58.1-150 Hz) in operation IEC 60068-2-6
Environmental Characteristic
3K3 C
Ip Degree Of Protection
IP20 IEC 60529 terminals) || IP50 IEC 60529 front panel) || IP30 IEC 60529 housing)
Pollution Degree
3 IEC 60664-1 || 3 UL 508
Ambient Air Temperature For Storage
-40-70 °C
Relative Humidity
93-97 % 25-55 °C IEC 60068-2-30

Documents

Data Sheet

Download

CAD Models

Trace parts
Trace parts
Download

Related products