Zelio, 3 phase supply control relay, range 220 to 480 VAC, sequence, phase failure, phase imbalance, voltage
RM35TF30
RM35TF30
RM35TF30
RM35TF30
RM35TF30
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
£50.40
1
Payment methods:
A total of 617 Parts In-Stock from 35 Distributors
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
€49.83

Additional Information

Part Number
RM35TF30
UNSPSC
39122331
Tariff Code
8537109170
Country of Origin
ID

Environment

Product Certifications
GL || UL || CSA || GOST || C-tick
Standards
IEC 60255-1
Non-Dissipating Shock Wave
4 kV
Dielectric Test Voltage
2 kV AC 50 Hz, 1 min
Electromagnetic Compatibility
emission standard for industrial environments conforming to IEC 61000-6-4 || emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3 || immunity for industrial environments conforming to IEC 61000-6-2
Shock Resistance
15 gn 11 ms IEC 60255-21-1
Ambient Air Temperature For Operation
-20-50 °C
Vibration Resistance
0.35 mm 5-57.6 Hz)IEC 60068-2-6 || 1 gn 57.6-150 Hz)IEC 60255-21-1
Ip Degree Of Protection
IP20 IEC 60529 terminals) || IP30 IEC 60529 casing)
Pollution Degree
3 IEC 60664-1
Directives
89/336/EEC - electromagnetic compatibility || 73/23/EEC - low voltage directive
Ambient Air Temperature For Storage
-40-70 °C
Relative Humidity
95-95 % 55-55 °C IEC 60068-2-30

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1504008EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation
X
Circularity Profile
ENVEOLI1504008EN
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Complementary

Voltage Range
220...480 V phase to phase
Safety Reliability Data
MTTFd = 399.5 years || B10d = 360000
Minimum Switching Current
10 mA 5 V DC
Maximum Measuring Cycle
140 ms measurement cycle as true rms value
Control Circuit Voltage Limits
12 % + 10 % Un
Maximum Switching Current
5 A AC || 5 A DC
Hysteresis
2-2 %
Insulation Resistance
> 500 MOhm 500 V DC IEC 60255-5 || > 500 MOhm 500 V DC IEC 60664-1
Measurement Error
< 1 % over the whole range with voltage variation || 0.05 %/°C with temperature variation
Operating Rate
<= 360 operations/hour full load
Power Consumption In Va
0-22 VA 400 V AC 50 Hz
Output Contacts
2 C/O
Voltage Detection Threshold
< 194 V
Adjustment Of Asymmetry Threshold
5...15 % of Un selected
Marking
CE
Response Time
< 200 ms (in the event of a fault)
Operating Position
any position without derating
Utilisation Category
AC-12 IEC 60947-5-1 || AC-13 IEC 60947-5-1 || AC-14 IEC 60947-5-1 || AC-15 IEC 60947-5-1 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1
Net Weight
0.13 kg
Maximum Switching Voltage
250 V AC || 250 V DC
Measurement Voltage Limits
176-528 V AC
Reset Time
1500 ms at 480 V
Connections - Terminals
screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
[Ui] Rated Insulation Voltage
400 V IEC 60664-1
Overvoltage Category
III IEC 60664-1
Supply Voltage Limits
194-528 V AC, 3 phase
Mounting Support
35 mm symmetrical DIN rail conforming to IEC 60715
Nominal Output Current
5 A
Local Signalling
for power ON LED (green) || for relay ON LED (yellow) || for fault LED (yellow)
Mechanical Durability
30000000 cycles
Housing Material
self-extinguishing plastic
Control Circuit Frequency
50...60 Hz +/- 10 %
Threshold Adjustment Voltage
-20...-2 % in the range 380...480 V AC || 2...20 % of Un selected || -12...-2 % in the range 220 V AC || +2...+20 % in the range 220...440 V AC || +2...+10 % in the range 480 V AC
Width
35 mm
Tightening Torque
0.6-1 N.m IEC 60947-1
Electrical Durability
100000 cycles
Run-Up Delay At Power-Up
650 ms
Supply Frequency
50/60 Hz +/- 10 %
Repeat Accuracy
0.3 % time delay || 0.5 % input and measurement circuit

Specifications

Range Of Product
Harmony Control Relays
Measurement Range
220...480 V voltage AC
Switching Capacity In Va
1250 VA
Product Or Component Type
3-phase control relay
Relay Name
RM35TF
Contacts Type And Composition
2 C/O
Relay Type
multifunction control relay
Product Specific Application
for 3-phase supply
Time Delay Type
adjustable 0.1...10 s, +/- 10 % of the full scale value
Relay Monitored Parameters
undervoltage and overvoltage in window mode || phase sequence || phase failure detection || asymmetry
[Uc] Control Circuit Voltage
220...480 V

Documents

Data Sheet

Download

CAD Models

Trace parts
Trace parts
Download

Related products