3-phase control relay, Harmony Control Relays, 5A , 2NO, phase failure detection, 24..240V AC DC
RM35TM50MW
RM35TM50MW
RM35TM50MW
RM35TM50MW
RM35TM50MW
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€81.44
1
Payment methods:
A total of 227 Parts In-Stock from 22 Distributors
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
€60.83

Additional Information

Part Number
RM35TM50MW
UNSPSC
39122329
Tariff Code
8536490075
Country of Origin
ID

Environment

Product Certifications
GL || UL || GOST || C-tick || CSA
Standards
IEC 60255-6 || IEC 60034-11-2
Non-Dissipating Shock Wave
4 kV
Dielectric Test Voltage
2 kV AC 50 Hz, 1 min
Electromagnetic Compatibility
emission standard for industrial environments conforming to IEC 61000-6-4 || emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3 || immunity for industrial environments conforming to IEC 61000-6-2
Immunity To Microbreaks
20 ms 20.4 V
Shock Resistance
15 gn 11 ms IEC 60255-21-1
Ambient Air Temperature For Operation
-20-50 °C
Vibration Resistance
0.35 mm 5-57.6 Hz)IEC 60068-2-6 || 1 gn 57.6-150 Hz)IEC 60255-21-1
Ip Degree Of Protection
IP20 IEC 60529 terminals) || IP30 IEC 60529 casing)
Pollution Degree
3 IEC 60664-1
Directives
73/23/EEC - low voltage directive || 89/336/EEC - electromagnetic compatibility
Ambient Air Temperature For Storage
-40-70 °C
Relative Humidity
95-95 % 55-55 °C IEC 60068-2-30

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1504008EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation
X
Circularity Profile
ENVEOLI1504008EN
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Complementary

Voltage Range
176...528 V
Minimum Switching Current
10 mA 5 V DC
[Uc] Control Circuit Voltage
<= 3.6 V temperature control circuit T1-T2 terminals open)
Maximum Switching Current
5 A AC || 5 A DC
Insulation Resistance
> 500 MOhm 500 V DC between supply and relay output IEC 60255-5 || > 500 MOhm 500 V DC between measurement and relay output IEC 60664-1 || > 1 MOhm 500 V DC between supply and measurement IEC 60255-5 || > 500 MOhm 500 V DC between supply and relay output IEC 60664-1 || > 500 MOhm 500 V DC between measurement and relay output IEC 60255-5 || > 1 MOhm 500 V DC between supply and measurement IEC 60664-1
Operating Rate
<= 360 operations/hour full load
Power Consumption In Va
0-4 VA 24...240 V AC
Output Contacts
2 NO
Marking
CE
Response Time
> 50 ms (input Y1 (contact Y1-T1) and push-button)
Operating Position
any position without derating
Resistance Across Terminals
602 mOhm
Short-Circuit Current
0.007 A temperature sensing circuit T1-T2 terminals short circuited)
Utilisation Category
AC-12 IEC 60947-5-1 || AC-13 IEC 60947-5-1 || AC-14 IEC 60947-5-1 || AC-15 IEC 60947-5-1 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1
Net Weight
0.13 kg
Maximum Switching Voltage
250 V AC || 250 V DC
Measurement Voltage Limits
176-528 V AC
Reset Time
10000 ms output
Connections - Terminals
screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
Reset Threshold
1650 Ohm +/- 10 % temperature control circuit
[Ui] Rated Insulation Voltage
400 V IEC 60664-1
Maximum Resistance
1500 Ohm temperature sensor 20 °C
Overvoltage Category
III IEC 60664-1
Tripping Threshold
3100 Ohm +/- 10 % temperature control circuit
Supply Voltage Limits
20.4-264 V AC || 20.4-264 V DC
Mounting Support
35 mm symmetrical DIN rail conforming to IEC 60715
Nominal Output Current
5 A
Local Signalling
for power ON LED (green) || for phase of relay (R2) LED (yellow) || for temperature of relay (R1) LED (yellow)
Mechanical Durability
30000000 cycles
Housing Material
self-extinguishing plastic
Control Circuit Frequency
50...60 Hz +/- 10 %
Width
35 mm
Tightening Torque
0.6-1 N.m IEC 60947-1
Maximum Power Consumption In W
0.5 W DC
Electrical Durability
10000 cycles
Run-Up Delay At Power-Up
500 ms
Supply Frequency
50/60 Hz +/- 10 %

Specifications

Range Of Product
Harmony Control Relays
Measurement Range
208...480 V voltage AC || 0...20 Ohm short-circuit detection
Switching Capacity In Va
1250 VA
Product Or Component Type
motor temperature control relay
Relay Name
RM35TM
Contacts Type And Composition
2 NO
Relay Type
motor temperature control relay
Product Specific Application
for 3-phase supply
Time Delay Type
fixed 0.3 s
Relay Monitored Parameters
phase sequence || motor temperature via PTC probe || phase failure detection
[Uc] Control Circuit Voltage
24...240 V

Documents

Data Sheet

Download

CAD Models

Trace parts
Trace parts
Download

Related products