voltage control relay, Harmony Control Relays, 5A, 2CO, 220…480V AC
RM35UB330
RM35UB330
RM35UB330
RM35UB330
RM35UB330
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€120.81
1
Payment methods:
A total of 53 Parts In-Stock from 22 Distributors
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
€54.76

Additional Information

Part Number
RM35UB330
UNSPSC
39122331
Tariff Code
8536490075
Country of Origin
ID

Environment

Product Certifications
C-tick || GOST || CSA || GL || UL
Standards
IEC 60255-1
Non-Dissipating Shock Wave
4 kV
Dielectric Test Voltage
2 kV AC 50 Hz, 1 min
Electromagnetic Compatibility
emission standard for industrial environments conforming to IEC 61000-6-4 || emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3 || immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Shock Resistance
5 gn IEC 60068-2-27
Ambient Air Temperature For Operation
-20-50 °C
Vibration Resistance
0.35 mm 5-57.6 Hz)IEC 60068-2-6 || 1 gn 57.6-150 Hz)IEC 60255-21-1
Ip Degree Of Protection
IP20 IEC 60529 terminals) || IP30 IEC 60529 casing)
Pollution Degree
3 IEC 60664-1
Directives
73/23/EEC - low voltage directive || 89/336/EEC - electromagnetic compatibility
Ambient Air Temperature For Storage
-40-70 °C
Relative Humidity
95-95 % 55-55 °C IEC 60068-2-30

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1504008EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation
X
Circularity Profile
ENVEOLI1504008EN
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Complementary

[Us] Rated Supply Voltage
220...480 V AC 50/60 Hz +/- 10 %
Safety Reliability Data
B10d = 300000 || MTTFd = 319.6 years
Maximum Measuring Cycle
150 ms measurement cycle as true rms value
Hysteresis
2-2 %
Insulation Resistance
> 500 MOhm 500 V DC IEC 60255-5 || > 500 MOhm 500 V DC IEC 60664-1
Measurement Error
< 1 % over the whole range with voltage variation || 0.05 %/°C with temperature variation
Operating Rate
<= 360 operations/hour full load
Output Contacts
1 C/O + 1 C/O, 1 per threshold
Response Time
< 200 ms (in the event of a fault)
Operating Position
any position without derating
Net Weight
0.08 kg
Maximum Switching Voltage
250 V AC/DC
Reset Time
1500 ms time delay
Run-Up Delay At Power-Up
650 ms
Connections - Terminals
screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...2 x 2.5 mm² AWG 24...AWG 12) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
Functionality
overvoltage and undervoltage detection
[Ui] Rated Insulation Voltage
400 V IEC 60664-1
Overvoltage Category
III IEC 60664-1
Quality Labels
CE
Supply Voltage Limits
194-528 V AC
Mounting Support
35 mm symmetrical DIN rail conforming to IEC 60715
Nominal Output Current
5 A
Local Signalling
for power ON LED (green) || for relay ON LED (yellow)
Mechanical Durability
30000000 cycles
Voltage Detection Threshold
194 V
Compatibility Code
RM3
Housing Material
self-extinguishing plastic
Control Circuit Frequency
50...60 Hz +/- 15 %
Threshold Adjustment Voltage
2...20 % of Un selected || -12...-2 % in the range 220 V AC || +2...+10 % in the range 480 V AC
Measurement Accuracy
+/- 10 % of the full scale value
Width
35 mm
Tightening Torque
0.6-1 N.m IEC 60947-1
Electrical Durability
10000 cycles
Repeat Accuracy
+/- 0.5 % input and measurement circuit || +/- 1 % time delay

Specifications

Minimum Switching Current
10 mA 5 V DC
Maximum Switching Current
5 A AC/DC
Range Of Product
Harmony Control Relays
Measurement Range
194...528 V voltage AC 50/60 Hz
Power Consumption In Va
0-22 VA 400 V AC 50 Hz
Switching Capacity In Va
1250 VA
Product Or Component Type
voltage control relay
Utilisation Category
AC-12 IEC 60947-5-1 || AC-13 IEC 60947-5-1 || AC-14 IEC 60947-5-1 || AC-15 IEC 60947-5-1 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1 || DC-14 IEC 60947-5-1
Relay Name
RM35UB3
Contacts Type And Composition
2 C/O
Relay Type
voltage control relay
Product Specific Application
for 3-phase supply
Time Delay Type
adjustable 0.3...30 s, 0 + 10 % on crossing the threshold
Relay Monitored Parameters
overvoltage and undervoltage between phases

Documents

Data Sheet

Download

CAD Models

Trace parts
Trace parts
Download

Related products