RMPT13BD

Converter for Optimum Pt100 probes, Harmony Analog, temperature transmitter, 40...40 degree COr 40...104 degree F
RMPT13BD
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up

Environment

Disturbance Radiated/Conducted
CISPR 11 || CISPR 22 group 1 - class B
Product Certifications
CSA || UL || GL
Pollution Degree
2 IEC 60664-1
Ambient Air Temperature For Storage
-40-85 °C
Standards
EN/IEC 60751 || EN/IEC 60584-1 || DIN 43760 || EN/IEC 60947-1
Ambient Air Temperature For Operation
0-50 °C mounting side by side || 0-60 °C 2 cm spacing
Electromagnetic Compatibility
electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2 || electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
Fire Resistance
850 °C IEC 60695-2-1 || 850 °C UL
Shock Resistance
50 gn 11 ms IEC 60068-2-27
Vibration Resistance
5 gn 10-100 Hz)IEC 60068-2-6
Resistance To Fast Transients
1 kV IEC 61000-4-4 on input-output) || 2 kV IEC 61000-4-4 on power supply)
Ip Degree Of Protection
IP20 terminal block) || IP50 housing)

Contractual warranty

Warranty
18 months

Offer Sustainability

China Rohs Regulation
X
Circularity Profile
ENVEOLI1607005EN
Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1607005EN
Sustainable Offer Status
Green Premium product
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.

Complementary

[Us] Rated Supply Voltage
24 V DC non isolated +/- 20 %
Current Consumption
<= 40 mA voltage output || <= 60 mA current output
Safety Reliability Data
B10d = 40564 || MTTFd = 43.9 years
Measurement Error
+/- 0.5 % of full scale 3 or 4 wires)20 °C || +/- 1 % of full scale 2 wires)20 °C || +/- 10 % of full scale20 °C electromagnetic interference of 10 V/m)
Surge Withstand
0.5 kV 1.2/50 µs IEC 61000-4-5
Clamping Connection Capacity
1 x 2.5 mm² || 2 x 1.5 mm²
Maximum Wiring Resistance
0.2 Ohm 2 wires
Local Signalling
for power ON LED (green)
Temperature Coefficient
150 ppm/°C
Protection Type
reverse polarity protection on output || overvoltage protection on output (+/- 30 V) || reverse polarity protection on power supply || short-circuit protection on output
[Ui] Rated Insulation Voltage
2000 V
Marking
CE
Analogue Output Voltage
-15...-11 V no input or input wire broken || 11...15 V no input or input wire broken
Net Weight
0.12 kg
Fixing Mode
clip-on 35 mm symmetrical DIN rail) || fixed mounting plate)
Tightening Torque
0.6-1.1 N.m
Analogue Output Current
-30-0 mA no input or input wire broken || 22-30 mA no input or input wire broken
Repeat Accuracy
+/- 0.2 % full scale 20 °C || +/- 0.6 % full scale 60 °C

Specifications

Range Of Product
Harmony Analog
Analogue Output Type
current 4...20 mA <= 500 Ohm || voltage 0...10 V >= 100 kOhm
Product Or Component Type
converter for Optimum Pt100 probes
Analogue Input Type
temperature probe - 40...40 °C/- 40...104 °F Pt 100 2, 3 or 4 wires

Documents

Data Sheet

Download

CAD Models

Trace parts
Trace parts
Download

Related products