Schneider Electric

XCKJ110513H7

Limit switch, XC Standard, XCKJ, steel roller lever, 1C/O, snap action, 1/2NPT
XCKJ110513H7
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
Send request for price

Additional Information

Part Number
XCKJ110513H7
UNSPSC
39122213
Tariff Code
8536509055
Country of Origin
FR

Specifications

Type Of Approach
lateral approach, 1 or 2 programmable direction
Series Name
standard format
Contacts Type And Composition
1 C/O
Movement Of Operating Head
rotary
Body Type
plug-in body
Range Of Product
Telemecanique Limit switches XC Standard
Contact Operation
snap action
Fixing Mode
by the body
Type Of Operator
spring return roller lever metal
Body Material
zamak
Cable Entry
1 entry tapped for 1/2" NPT cable gland
Product Or Component Type
limit switch
Head Material
zamak
Material
metal
Device Short Name
XCKJ
Number Of Poles
1
Head Type
rotary head

Contractual warranty

Warranty
18 months

Complementary

Switch Actuation
by 30° cam
[Ui] Rated Insulation Voltage
300 VUL 508 || 500 V 3)IEC 60947-1 || 300 VCSA C22.2 No 14
Height
84-84 mm
Terminals Description Iso N°1
(11-12)NC || (13-14)NO
Short-Circuit Protection
10 A cartridge fuse gG
Electrical Durability
5000000 cycles, DC-13, inductive, 120 V, 4 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C || 5000000 cycles, DC-13, inductive, 24 V, 10 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C || 5000000 cycles, DC-13, inductive, 48 V, 7 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C
Positive Opening
without
Contacts Insulation Form
Zb
[Ie] Rated Operational Current
3 A 240 V, AC-15, A300 EN/IEC 60947-5-1 appendix A || 0.27 A 250 V, DC-13, Q300 EN/IEC 60947-5-1 appendix A
Electrical Connection
screw-clamp terminals 1 x 0.75...2 x 1.5 mm²
Number Of Steps
1
Mechanical Durability
30000000 cycles
Maximum Actuation Speed
1.5 m/s
[Ithe] Conventional Enclosed Thermal Current
10 A
Width
43 mm
Depth
36 mm
Minimum Torque For Tripping
0.25 N.m
Net Weight
0.49 kg
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60664 || 6 kV IEC 60947-1
Maximum Resistance Across Terminals
25 MOhm IEC 60255-7 category 3

Offer Sustainability

Environmental Disclosure
ENVPEP110614EN
Eu Rohs Directive
Not applicable, out of EU RoHS legal scope
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Environment

Product Certifications
UL || CSA || CCC
Ik Degree Of Protection
IK07 EN 50102
Ambient Air Temperature For Operation
-25-70 °C
Ambient Air Temperature For Storage
-40-70 °C
Overvoltage Category
class I IEC 61140 || class I NF C 20-030
Standards
CSA C22.2 No 14 || EN 60947-5-1 || CENELEC EN 50041 || EN 60204-1 || IEC 60947-5-1 || UL 508 || IEC 60204-1
Shock Resistance
50 gn 11 ms IEC 60068-2-27
Vibration Resistance
25 gn 10-500 Hz)IEC 60068-2-6
Protective Treatment
TH
Ip Degree Of Protection
IP66 conforming to IEC 60529