XCKP2121P16

Limit switch, Limit switches XC Standard, XCKP, thermoplastic plastic roller lever plung. Hor, 1NC+1 NO, snap, M16
XCKP2121P16
XCKP2121P16
XCKP2121P16
XCKP2121P16
XCKP2121P16
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up

Specifications

Movement Of Operating Head
linear
Range Of Product
Telemecanique Limit switches XC Standard
Fixing Mode
by the body
Type Of Operator
spring return roller lever plunger thermoplastic
Sensor Design
compact form E CENELEC EN 50047
Product Or Component Type
limit switch
Head Material
zamak
Material
plastic
Head Type
plunger head
Type Of Approach
lateral approach, 1 direction
Series Name
standard format
Contacts Type And Composition
1 NC + 1 NO
Body Type
fixed
Contact Operation
snap action
Body Material
plastic
Device Short Name
XCKP
Number Of Poles
2

Contractual warranty

Warranty
18 months

Complementary

Height
65-65 mm
Terminals Description Iso N°1
(21-22)NC || (13-14)NO
Short-Circuit Protection
10 A cartridge fuse gG
Electrical Connection
screw-clamp terminals 1 x 0.34...2 x 1.5 mm²
Cable Entry
1 entry tapped for M16 x 1.5 cable gland 4-8 mm
Net Weight
0.105 kg
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60664 || 6 kV IEC 60947-1
Switch Actuation
by 30° cam
[Ui] Rated Insulation Voltage
300 VUL 508 || 500 V 3)IEC 60947-1 || 300 VCSA C22.2 No 14
Electrical Durability
5000000 cycles, DC-13, 120 V, 4 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C || 5000000 cycles, DC-13, 24 V, 10 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C || 5000000 cycles, DC-13, 48 V, 7 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C
Positive Opening Minimum Force
18 N
Positive Opening
with
Contacts Insulation Form
Zb
Mechanical Durability
15000000 cycles
Maximum Actuation Speed
1 m/s
Minimum Force For Tripping
6 N
Contact Code Designation
A300, AC-15 (Ue = 240 V), Ie = 3 A 10 A EN/IEC 60947-5-1 appendix A || Q300, DC-13 (Ue = 250 V), Ie = 0.27 A EN/IEC 60947-5-1 appendix A
Width
31 mm
Depth
30 mm
Repeat Accuracy
0.1 mm on the tripping points with 1 million operating cycles
Maximum Resistance Across Terminals
25 MOhm IEC 60255-7 category 3

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP110606EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Circularity Profile
ENVEOLI110603EN
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Environment

Product Certifications
CCC || CSA || UL
Ik Degree Of Protection
IK04 EN 50102
Ambient Air Temperature For Operation
-25-70 °C
Standards
EN 60204-1 || IEC 60204-1 || EN 60947-5-1 || IEC 60947-5-1 || CSA C22.2 No 14 || UL 508
Shock Resistance
50 gn 11 ms IEC 60068-2-27
Vibration Resistance
25 gn 10-500 Hz)IEC 60068-2-6
Ip Degree Of Protection
IP66 conforming to IEC 60529 || IP67 conforming to IEC 60529
Ambient Air Temperature For Storage
-40-70 °C
Electrical Shock Protection Class
class II IEC 61140 || class II NF C 20-030
Protective Treatment
TC

Documents

Data Sheet

Download

Related products