Specifications

Contacts Type And Composition
1 NC + 1 NO
Range Of Product
Telemecanique Safety switches XCS
Insulation
double insulated
Cable Entry
1 entry tapped Pg 11
Clamping Connection Capacity
1 x 0.5...2 x 1.5 mm² with or without cable end
Contact Operation
slow-break, break before make
Type Of Operator
spindle 80 mm
Electrical Connection
terminal
Product Or Component Type
guard switch
Component Name
XCSPR
Material
plastic
Number Of Poles
2
Head Type
turret head rotary axis

Contractual warranty

Warranty
18 months

Complementary

Height
96-96 mm
[Ui] Rated Insulation Voltage
300 VUL 508 || 300 VCSA C22.2 No 14 || 500 V 3)EN/IEC 60947-1
Short-Circuit Protection
10 A cartridge fuse gG (gl)
Positive Opening
with NC contact
Positive Opening Minimum Torque
0.25 N.m
Mechanical Durability
1000000 cycles
[Ithe] Conventional Enclosed Thermal Current
10 A
Safety Reliability Data
B10d = 5000000 value given for a life time of 20 years limited by mechanical or contact wear
Enclosure Material
polyamide PA66 fibre glass impregnated
Lever Material
stainless steel
Contact Code Designation
A300, AC-15 (Ue = 120 V, Ie = 6 A)EN/IEC 60947-5-1 || A300, AC-15 (Ue = 240 V, Ie = 3 A)EN/IEC 60947-5-1 || Q300, DC-13 (Ue = 125 V, Ie = 0.55 A)EN/IEC 60947-5-1 || Q300, DC-13 (Ue = 250 V, Ie = 0.27 A)EN/IEC 60947-5-1
Tripping Angle
5 °
Width
30 mm
Depth
110 mm
Cable Outer Diameter
7-10 mm
Minimum Torque For Tripping
0.1 N.m
Net Weight
0.137 kg
[Uimp] Rated Impulse Withstand Voltage
6 kV EN/IEC 60947-5-1
Maximum Resistance Across Terminals
30 mOhm EN/IEC 60947-5-4
Safety Level
can reach category 4 with the appropriate monitoring system and correctly wired EN/ISO 13849-1 || can reach PL = e with the appropriate monitoring system and correctly wired EN/ISO 13849-1 || can reach SIL 3 with the appropriate monitoring system and correctly wired IEC 61508

Offer Sustainability

Circularity Profile
ENVEOLI110603EN
Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP110606EN
Sustainable Offer Status
Green Premium product
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes

Environment

Product Certifications
UL || CSA || BG
Ambient Air Temperature For Operation
-25-70 °C
Ambient Air Temperature For Storage
-40-70 °C
Standards
EN/IEC 60947-5-1 || CSA C22.2 No 14 || EN/ISO 12100 || EN/IEC 60204-1 || EN 1088/ISO 14119 || UL 508 || EN/IEC 60947-5-4
Electrical Shock Protection Class
class II EN/IEC 61140
Shock Resistance
50 gn 11 ms IEC 60068-2-27
Vibration Resistance
50 gn 10-500 Hz)IEC 60068-2-6
Protective Treatment
TH || TC
Ip Degree Of Protection
IP67 conforming to IEC 60529