Tripp Lite

PDUMH20-ISO

1.92kW Single-Phase Metered PDU + Isobar Surge Suppression, 3840 Joules, 120V Outlets (12 5-20R, 2 5-15R), L5-20P/5-20P, 15ft Cord, 1U Rack-Mount
PDUMH20-ISO
PDUMH20-ISO
PDUMH20-ISO
PDUMH20-ISO
PDUMH20-ISO
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Overview

UPC Code
037332185709
PDU Type
Metered

Output

Frequency Compatibility
50 / 60 Hz
Output Capacity Details
2.03kW (127V), 1.92kW (120V), 1.6kW (100V) / 20A total capacity (Agency de-rated to 16A); 16A max per 5-15/20R outlet; 12A max per 5-15R outlet
Output Receptacles
(2) 5-15R; (12) 5-15/20R
Output Nominal Voltage
100; 120; 127
Overload Protection
20A circuit breaker

Input

PDU Input Voltage
100; 120; 127
Recommended Electrical Service
20A 120V; For best results, connect the PDU only to true sine wave mains, generator or UPS power source (avoid connecting to UPS systems producing modified sine wave, PWM sine wave and other non-sinusoidal waveforms)
Maximum Input Amps
20
Maximum Input Amps Details
Agency de-rated to 16A continuous
PDU Plug Type
NEMA 5-20P; NEMA L5-20P
Input Phase
Single-Phase
Input Cord Length (ft.)
15

User Interface, Alerts & Controls

Front Panel LCD Display
Two digit current meter reports PDU output load in amps
Front Panel LEDs
Set of 3 diagnostic LEDs continuously report status for LINE OK (green), suppressor or wiring FAULT (red) and PROTECTION PRESENT (green)
Switches
No power switch

Surge / Noise Suppression

AC Suppression Joule Rating
3840
AC Suppression Response Time
NM = 0 ns. CM = <1 ns
Protection Modes
Includes full normal mode (H-N) and common mode (N-G / H-G) line surge suppression
Clamping Voltage (RMS)
140
AC Suppression Surge Current Rating
60,000 amps
EMI / RFI Filtering
40-80 dB
Immunity
Conforms to IEEE 587 / ANSI C62.41
Automatic Shut-Off
Yes

Physical

Form Factors Supported
1U rackmount, 0U vertical rackmount, wall-mount, and under-counter installation
Material of Construction
Metal
Minimum Required Rack Depth (inches)
9.5
PDU Form Factor
Horizontal (1U)
Shipping Dimensions (hwd / in.)
2.25 x 20.50 x 10.00
Shipping Weight (lbs.)
7.10
Unit Dimensions (hwd / in.)
1.75 x 17.5 x 4.5
Unit Weight (lbs.)
4.6

Environmental

Storage Temperature Range
-30°C to +50°C (-22°F to +122°F)
Relative Humidity
5 to 95% non-condensing
Operating Elevation (ft.)
0-10,000
Operating Elevation (m)
0-3000

Special Features

TVSS Grounding
Rear grounding lug

Certifications

Certifications
Tested to UL1449 3rd Edition (USA) and CSA (Canada), RoHS Compliant

Warranty

Product Warranty Period (Worldwide)
2-year limited warranty

Documents

Data Sheet

Download